Error Messages (3 of 4)
Error Displayed
Description of Error
The control is no longer able to read the Outdoor sensor due to an open circuit. In this case the
control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair
the problem. To clear the error message from the control after the sensor has been repaired, press
either the Menu or Item button.
The control is no longer able to read the Mixing Supply sensor due to a short circuit. In this case, if
the Boil SENS item is set to SUP, the control will operate the mixing device at a fi xed 15% of output
as long as there is a Mixing Demand. If the Boil SENS item is set to RET or NONE, the control
operates the mixing device at a fi xed 30% of output as long as there is a mixing demand. Locate and
repair the problem. To clear the error message from the control after the sensor has been repaired,
press either the Menu or Item button.
The control is no longer able to read the Mixing Supply sensor due to an open circuit. In this case, if
the Boil SENS item is set to SUP, the control will operate the mixing device at a fi xed 15% of output
as long as there is a Mixing Demand. If the Boil SENS item is set to RET or NONE, the control
operates the mixing device at a fi xed 30% of output as song as there is a Mixing Demand. Locate and
repair the problem. To clear the error message from the control after the sensor has been repaired,
press either the Menu or Item button.
The control is no longer able to read the Boiler sensor due to a short circuit. If the Boiler Minimum setting
is higher than 100°F (38°C) the control closes the boiler contact when the mixing device starts to operate.
The boiler temperature is limited by the operating aquastat. If the Boiler Minimum setting is lower than
100°F (38°C) the control does not operate the boiler contact. Locate and repair the problem. To clear the
control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the boiler sensor due to an open circuit. If the Boiler Minimum
setting is higher than 38°C the control closes the boiler contact when the mixing device starts to
operate. The boiler temperature is limited by the operating aquastat. If the Boiler Minimum setting is
lower than 38°C the control does not operate the boiler contact. Locate and repair the problem. If the
Boiler Sensor was deliberately not installed, set the Boil SENS item to NONE. To clear the control
after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the 10K input because of a short circuit. The control will continue
to operate as if there was nothing connected to the 10K input. Locate and repair the problem. To
clear the error message from the control after the sensor has been repaired, press either the Menu
or Item button.
The control is no longer able to read the 10K input because of an open circuit. The control will continue
to operate as if there was nothing connected to the 10K input. Locate and repair the problem. If a 10K
sensor was deliberately not installed, set the 10K item to NONE. To clear the error message from the
control after the sensor has been repaired, press either the Menu or Item button.
The air sensor in the RTU is being read as a short circuit. The RTU will continue operation using all
remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the
RTU was not connected to the control. This error message can be cleared once the sensor has been
repaired. To clear the error message from the control, press either the Menu or Item button.
The air sensor in the RTU is being read as an open circuit. The RTU will continue operation using all
remaining sensors. If all of the sensors are unavailable, the control will continue to operate as if the
RTU was not connected to the control. This error message can be cleared once the sensor has been
repaired. To clear the error message from the control, press either the Menu or Item button.
The Remote Sensor 1 attached to the RTU is being read as a short circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem. To clear the error message from the
control, press either the Menu or Item button. REMOTE 1 ≠ NONE
The Remote Sensor 1 attached to the RTU is being read as an open circuit. The RTU will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if the RTU was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem. To clear the error message from the
control, press either the Menu or Item button. REMOTE 1 ≠ NONE