Monitor Menu (2 of 2)
Note: To clear the recorded information in the specific Item field, press and hold
Item Field
Error Messages (1 of 4)
Error Displayed
© 2003
D 362e - 06/03
Access
Level
The lowest temperature recorded at the boiler sensor since this
item was last cleared.
Boil SENS ≠ NONE
This item is an adjustable warning that can only be viewed if the
10K item has been set to INDR. If the air temperature measured
by the indoor air sensor exceeds this setting, the control will
display a warning message.
10K = INDR
This item is an adjustable warning that can only be viewed if the
10K item has been set to INDR. If the air temperature measured
by the indoor air sensor drops below this setting, the control will
display a warning message.
10K = INDR
This item is an adjustable warning. If either the boiler or mixing
supply temperature does not begin to increase within the set
amount of time when required, the control will display a warning
message.
The number of times that the microprocessor in the control has
reset since this item was last cleared. The control will reset itself if
it has experienced some form of interference that has disrupted its
operation. This can be used to give an indication for the quality of
the electrical environment that the control has been installed in.
The number of times that the microprocessor in the control has
been powered up since this item was last cleared. The number
will increase if there is a lowering of the input voltage beyond the
control's usable range. This item can be used as an indication of
the quality of the power source.
The number of times that a communication error has been
detected between the control and either an RTU or RDM since
this item was last cleared. If the wires between the control and the
tN1/tN2 device are run in a noisy electrical environment, this can
cause interference in the communication between the control and
the tN1/tN2 device.
The control was unable to store a piece of information into its EEPROM. This error can be caused
by a noisy power source. The control will display the error message and will continue to operate as
normal. Pressing either the Menu or Item button will clear this error.
The control was unable to read a piece of information stored in the Adjust Menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust Menu. The control
will stop operation until all of the items available in the Adjust Menu of the control have been checked
by the user or installer.
Note: Access level must be ADV in order to clear the error.
The control was unable to read a piece of information stored in the Monitor Menu. Because of this,
the control was required to load the factory settings into all of the items in the Monitor Menu. The
control will continue to display the error message until all of the items available in the Monitor Menu
of the control have been checked by the user or installer.
Note: Access level must be ADV in order to clear the error.
and .
Description
Description of Error
26 of 32
Range
-31 to 266°F
(-35 to 130°C)
50 to 153°F
(10 to 66°C)
Default = 110°F (43°C)
0 to 81°F
(-18 to 27°C)
Default = 45°F (7°C)
3 to 40 min, OFF
Default = OFF
0 - 255
0 - 255
0 - 255