Kanmor Mixing Control 362e Data Brochure page 15

Table of Contents

Advertisement

Boiler
If the boiler is connected to the Boiler terminals (6 and 7), make sure power to the boiler circuit is off and install a jumper
between the terminals. When the boiler circuit is powered up, the boiler should fire. If the boiler does not turn on, refer to
any installation or troubleshooting information supplied with the boiler. (The boiler may have a flow switch that prevents
firing until the boiler pump is running.) If the boiler operates properly, disconnect the power and remove the jumper.
Mixing Valve Actuator
If a floating action actuating motor circuit is connected to the Pwr Mix, Opn, and Cls terminals (8, 9, and 10), make sure
power to the motor circuit is off and install a jumper between the Pwr Mix and Opn terminals (8 and 9). When the circuit is
powered up, the actuator should move in the opening direction. If it does not, check the wiring between the terminals and
the actuating motor. Refer to any installation or troubleshooting information supplied with the motor. If the motor closes
instead of opening, the wiring of the actuating motor must be reversed. If the valve opens correctly, turn off the power to
the circuit and remove the jumper. Install a jumper between the Pwr Mix and Cls terminals (8 and 10). When the circuit
is powered up, the valve should move in the closing direction. If it does not, check the wiring between the terminals and
the actuating motor. Refer to any installation or troubleshooting information supplied with the motor. If the motor closes
correctly, turn off the power to the circuit and remove the jumper.
Connecting The Control
Make sure all power to the devices and terminal blocks is off and remove any
remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their
respective headers on the control and then pushing the terminal blocks into the
headers. The terminal blocks should snap fi rmly into place.
Install the supplied safety dividers between the unpowered sensor inputs and the
powered wiring chambers.
Apply power to the control. The operation of the control on power up is described in
the Sequence of Operation section of this brochure.
Cleaning
The Control's exterior can be cleaned using a damp cloth. Moisten cloth with water and wring out prior to wiping control. Do not
use solvents or cleaning solutions.
15 of 32
© 2003
D 362e - 06/03

Advertisement

Table of Contents
loading

Related Products for Kanmor Mixing Control 362e

Table of Contents