14.5 Setting the switch points

GEMÜ 651 provides the possibility of proportionally setting the switch points for the OPEN
and CLOSED feedback to the programmed stroke.
Example:
Switch point OPEN 25 %,
Switch point CLOSED 12 %
Stroke
Switch
point
OPEN
Switch
point
CLOSED
These switch point distances enable compensation of operational changes such as
diaphragm swelling during sterilisation and thus ensure reliable end position feedback.
The switch points can be set via the parameter bits (see table "Switch points" in chapter

14.6 "AS-Interface data" ).

14.6 AS-Interface data
Inputs AS-Interface (as seen from the AS-Interface master)
Bit
Function
DI0
Indication of Open position
DI1
Indication of Closed position
DI2
Indication of operating mode
DI3
Error 2
FID
Error 1
Outputs AS-Interface (as seen from the AS-Interface master)
Bit
Function
DO0
Activation of pneum. outlet 2/4 (c.f. 1, 2)
(activation of pilot valve Y1/Y2)
DO1
Selection of programming mode
DO2
Selection of operating mode
DO3
non existent
Parameter outputs
Bit
Function
P0
Setting of switch points
P1
Setting of switch points
P2
Setting of switch points
651
Inputs / outputs
Logic
0 = process valve not in Open position
1 = process valve in Open position
0 = process valve not in Closed position
1 = process valve in Closed position
0 = normal operation
1 = programming mode
see Error analysis table
see Error analysis table
Logic
0 = pneum. outlet 2 vented / outlet 4 pressurized
1 = pneum. outlet 2 pressurized / outlet 4 vented
0 = manual programming
1 = automatic programming
0 = normal operation
1 = programming mode
Logic
see Switch point table
see Switch point table
see Switch point table
56 / 68