Duct Mount 285 Annubar
S
4
TEP
CONTINUED
Recommended Installations
Gas Service
Secure the electronics above the sensor to prevent condensable liquids from collecting in
the impulse piping and the DP cell.
Liquid Service (up to 250 °F (121 °C))
Secure the electronics below the sensor to ensure that air will not be introduced into the
impulse piping or the electronics.
Figure 10. Gas
Steam or Liquid Service (above 250 °F (121 °C))
Mount the electronics below the process piping, adjust 10 to 15 degree above direct vertical
down. Route the impulse piping down to the electronics and fill the system with cool water
through the two tee fittings.
Figure 12. Horizontal Line
10
...
Quick Installation Guide
Figure 11. Liquid
Figure 13. Vertical Line
00825-0100-4031, Rev AA
April 2005