Addressing Example - Festo CPX-E-PN Translation Of The Original Instructions

Bus module
Hide thumbs Also See for CPX-E-PN:
Table of Contents

Advertisement

Function
The bus module counts as a module with 0 inputs and 0 outputs when the status bits and the I/O
diagnostic interface are deactivated.
Activated status bits occupy 8 inputs.
An activated I/O diagnostic interface occupies 16 inputs and 16 outputs.
The inputs and outputs of different module types are assigned separately from each other.
Addressing is generally carried out by the higher-order controller (in cases where a SIEMENS higher-
order controller is being used).
2.3.2

Addressing Example

Fig. 4
The address assignment for the system CPX-E pictured here, in a TIA portal with a SIEMENS PLC is
shown in è Tab. 7
Mod-
Module
ule no.
0
Bus module CPX-E-PN (with status bits)
1
Digital input module CPX-E-16DI
2
Digital output module CPX-E-8DO
3
Digital output module CPX-E-8DO
4
Analogue input module CPX-E-4AI-U-I
5
Analogue output module CPX-E-4AO-U-I
Tab. 7
10
1 Bus module CPX-E-PN (with status bits)
–Status bits activated
–I/O diagnostic interface deactivated
2 Digital input module CPX-E-16DI
3 Digital output module CPX-E-8DO
4 Digital output module CPX-E-8DO
5 Analogue input module CPX-E-4AI-U-I
6 Analogue output module CPX-E-4AO-U-I
Input address
Byte 68
Byte 1 
Byte 69 
Output address
 2
...
Byte 1
Byte 2
 76
...
Byte 64 
 71
...
Festo — CPX-E-PN — 2020-01a