Connecting the system
No.
Cable
3
PoE cable on hand
cable drum
tan-δ cable on hand
4
cable drum
At the PD-TaD 80:
5
6
HV connection cable of
the cable test van (on
cable drum rack)
7
See above
In the cable test van:
8
9
HV connection cable of
the cable test van (on
cable drum rack)
At the PD-TaD 80:
10
Short-circuit cable of
PD-TaD 80
At the far end of the test object:
11
12
42 / 74
Step
Connect the PoE cable:
to the connection box (PoE port) and
to PD-TaD (Power Box port).
This is used for power supply and data transmission at the same time.
Connect the tan-δ cable:
to the connection box (TD port) and
to the PD-TaD (VLF Generator port).
Connect the HF filter to the HV IN port.
Further information: Chapter Connecting the HF filter to the PD-TaD 80 (on
page 48)
Connect the screen of the HV connection cable to the Screen (HV Cable)
port.
Connect the HV connection cable to the HF filter on the HV IN port.
For titron® systems only:
If the connecting plug is inserted in the HV connection socket of the DU 80
discharge unit, unplug it and hang it in the holder.
Connect the HV connection cable to the DU 80 discharge unit.
Guide all connected cables through the cable outlet of the rear door and
close the rear door.
On the PD-TaD 80, remove the short-circuit cable from ports HV IN and
HV OUT.
Clean the cable termination of the phase to be tested carefully.
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
PD-TaD 80
822-188-3