Baur PD-TaD 80 User Manual page 21

Portable pd diagnostics system
Table of Contents

Advertisement

PD-TaD 80
No.
1
2
3
4
5
 Note that the calibrator must be removed from the test circuit before switching on the
high voltage source.
Note: After some time, the calibrator automatically switches off to extend the battery life. If
you have not yet completed the calibration, switch on the calibrator.
822-188-3
Element
Protective earthing port
(metal port)
Signal output (black port)
Display of selected charge in
[nC]
Range
Pos/Neg
On/Off
Function
Is used to connect the protective earthing
Is used for connection to the test object.
Is used for setting the calibration charge
Possible settings:
CAL1B: 0.10, 0.20, 0.50, 1.00, 2.00, 5.00, 10.00 nC
CAL1E: 0.50, 1.00, 2.00, 5.00, 10.00, 20.00, 50.00 nC
 Press briefly to set the polarity of the signal.
 To switch on, press briefly.
 To switch off, press for approx. 3 seconds.
Product information
21 / 74