Baur PD-TaD 80 User Manual page 39

Portable pd diagnostics system
Table of Contents

Advertisement

PD-TaD 80
No.
Cable
1
Protective earthing
cable of the VLF HV
generator
2
Protective earthing
cable of PD-TaD 80
(flat copper strip)
On the VLF HV generator:
3
Connection cable
C19 – C20G
On the laptop:
4
USB cable
5
Ethernet cable
At the PD-TaD 80:
6
PoE cable
7
8
HV connection cable of
the VLF HV generator
9
See above
10
Short-circuit cable of
PD-TaD 80
At the far end of the test object:
11
12
822-188-3
Step
Earth the VLF HV generator.
Further information: User manual for the respective VLF HV generator
Connect the PD-TaD 80 to the station earth (close to the test object cable
screen).
Further information: Chapter Earth system (on page 34)
If present, connect the external emergency off unit to the VLF HV generator
(
port).
If you are not using an external emergency off unit, ensure that a jumper
plug is inserted into the
Connect the VLF HV generator (mains supply) to the Power Box (port
depends on the connection cable).
Use the USB cable to connect the laptop to the VLF HV generator.
Use the supplied Ethernet cable to connect the laptop to the Power Box
(Laptop port).
If you do not want to run the laptop off its battery, connect the laptop to the
Power Box to establish a power supply. To do so, use the connection cable
with the C14G plug.
Connect the PoE cable:
to the Power Box (PD Detector port) and
to PD-TaD 80 (Power Box port)
This is used for power supply and data transmission at the same time.
Connect the HF filter to the HV IN port.
Further information: Chapter Connecting the HF filter to the PD-TaD 80 (on
page 48)
Connect the screen of the HV connection cable to the Screen (HV Cable)
port.
Connect the HV connection cable to the HF filter at the HV IN port.
Further information: Chapter Connecting the HF filter to the PD-TaD 80 (on
page 48)
On the PD-TaD 80, remove the short-circuit cable from ports HV IN and
HV OUT.
Clean the cable termination of the phase to be tested carefully.
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
Connecting the system
port on the VLF HV generator.
39 / 74