PD-TaD 80
Procedure
Important:
 To keep the connection cable between the PD-TaD and the test object short, place the
PD-TaD as close as possible to the test object.
To avoid interference due to partial discharge at the connection point, make sure the PD-
TaD is placed a sufficient distance away from metal and live parts.
If the connection point is higher up, put the PD-TaD on a substructure. Further
information: Chapter Securing the PD-TaD 80 to the cross beam (on page 33)
 Keep all connections as short as possible.
 Lay out the connection cables in such a way that no loops are created.
The numbering in the table gives the sequence of steps for connecting the test object.
No.
Cable
1
Protective and auxiliary
earthing cables of the
cable test van (on cable
drum rack)
2
Protective earthing
cable of PD-TaD 80
(flat copper strip)
In the cable test van on the connection box of the cable drum rack:
822-188-3
Step
Earth the cable test van.
Further information: Additional manual for systems with diagnostics functions
Connect the PD-TaD 80 to the station earth (close to the test object cable
screen).
Further information: Chapter Earth system (on page 34)
If present, connect the external emergency off unit to the connection box of
the cable drum rack (
port).
If you are not using an external emergency off unit, ensure that a jumper
plug is inserted into the
rack.
Connecting the system
port on the connection box of the cable drum
41 / 74