Please ensure that following steps are taken:
ó Check the gradient for drainage fl ow as recommended in Figure B.
ó Provide clearance for easy servicing and optimal air fl ow as shown in Figure C.
FIGURE B
ó The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return
air.
FIGURE C
CEILING EXPLORED TYPE
ó Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for
piping and drainage installation. The unit must be a large distance away from the door.
Min 400mm
Min 300mm
PULL
PULL
PULL
PULL
FLOOR STANDING TYPE
PULL
Max 250mm
UTENSILS, FURNITURES OR BUILT-IN
ARCHITECTUAL FEATURES MUST NOT
PROTURDE MORE THAN 250.0MM.
Page 33
PULL
PULL
PULL
Min 10mm
Min 1.0m