McQuay M4AC080C Installation And Operation Manual

McQuay M4AC080C Installation And Operation Manual

Air-cooled mini chiller and heat pump

Advertisement

Библиотека СОК 
Product, Installation and Operation Manual
Air-Cooled Mini Chiller and Heat Pump
M4AC 080 ÷ 150 C
Cooling capacity from 22,4 to 40,0 kW
M4AC 080 ÷ 150 CR
Cooling capacity from 21,7 to 38,7 kW
Heating capacity from 25,6 to 41,5 kW
50 Hz – HFC 407 C refrigerant
309 B/C – 03/03 A
Date: March 2003
Supersedes:
none

Advertisement

Table of Contents
loading

Summary of Contents for McQuay M4AC080C

  • Page 1 Библиотека СОК  Product, Installation and Operation Manual 309 B/C – 03/03 A Date: March 2003 Supersedes: none Air-Cooled Mini Chiller and Heat Pump M4AC 080 ÷ 150 C Cooling capacity from 22,4 to 40,0 kW M4AC 080 ÷ 150 CR Cooling capacity from 21,7 to 38,7 kW Heating capacity from 25,6 to 41,5 kW 50 Hz –...
  • Page 2 ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?
  • Page 3 Introduction For years, McQuay international has earned a reputation for providing the industry with various highest quality and most technologically advanced air conditioning systems. Now McQuay is proud to introduce the new generation mini air- cooled chiller-M4AC C series. Inherited from the advantage of the earlier product experiences and introduced the most up-to-date technology, the new M4AC C series are designed with the always-in-mind concept - to satisfy customers’...
  • Page 4 Stainless steel taper threaded fittings target convenient disassembly or assembly. For M4AC080C/CR to M4AC150C/CR, expansion chamber, water pump and water flow switch are already equipped in this compact packaged unit with top air discharge. Both front and rear sides can be served as access to performing wiring and maintenance.
  • Page 5: General Specification

    General Specification Compressor McQuay Mini Chillers M4AC080C(R) to M4AC150C(R) are equipped with highly efficient, reliable and silence scroll compressors. Air-Cooler Condenser The air-cooled condenser coil consists of staggered rows of 3/8’ ’ O.D. seamless copper tube, mechanically expanded into die formed aluminum fins to ensure optimum heat exchange capability.
  • Page 6 Controller The controller accomplishes its control function with its built-in microprocessor. The two parameters, temperature and water flow rate, have been factory set before shipment, no need for users to reset them. The controller will display unit operation status to favor specialized personnel to monitor unit operating condition for maintenance if necessary. When the system is cut off due to malfunction, the controller will display the corresponding failure code for easy trouble shooting.
  • Page 7 Cooling Only Unit MODEL M4AC080C M4AC100C kcal/hr 19.260 22.960 NOMINAL COOLING CAPACITY Watt 22.400 26.700 MATERIAL Electro-galvanised Mild Steel FINISH Polyester Power CASING THICKNESS HEIGHT (H) mm (in) 1260 (49.6) TOTAL WIDTH (W) mm (in) 1500 (59.1) UNIT DIMENSION DEPTH (D) mm (in) 900 (35.4)
  • Page 8 Cooling Only Unit MODEL M4AC120C M4AC150C kcal/hr 28.720 34.390 NOMINAL COOLING CAPACITY Watt 33.400 40.000 MATERIAL Electro-galvanised Mild Steel FINISH Polyester Power CASING THICKNESS HEIGHT (H) mm (in) 1260 (49.6) TOTAL WIDTH (W) mm (in) 1800 (70.9) UNIT DIMENSION DEPTH (D) mm (in) 1150 (45.3) NET WEIGHT...
  • Page 9 Heat Pump Unit MODEL M4AC080CR M4AC100CR kcal/hr 18660 22180 NOMINAL COOLING CAPACITY Watt 21.700 25.800 kcal/hr 22.010 25.970 NOMINAL HEATING CAPACITY Watt 25.600 30.200 MATERIAL Electro-galvanised Mild Steel FINISH Polyester Power CASING THICKNESS TOTAL HEIGHT (H) mm (in) 1260 (49.6) UNIT WIDTH (W) mm (in)
  • Page 10 Heat Pump Unit MODEL M4AC120CR M4AC150CR kcal/hr 27.690 33.280 NOMINAL COOLING CAPACITY Watt 32.200 38.700 kcal/hr 31.210 35.680 NOMINAL HEATING CAPACITY Watt 36.300 41.500 MATERIAL Electro-galvanised Mild Steel CASING FINISH Polyester Power THICKNESS TOTAL HEIGHT (H) mm (in) 1260 (49.6) UNIT WIDTH (W) mm (in)
  • Page 11 Cap.ty input Cap.ty input 23,4 22,1 21,2 20,1 18,7 24,2 22,9 22,0 20,8 19,5 24,6 23,3 22,4 21,3 19,9 M4AC080C 25,0 23,7 22,9 21,7 20,2 10,0 25,6 24,2 23,4 22,2 10,1 20,8 10,7 26,3 25,0 10,1 24,2 10,8 22,9...
  • Page 12: Cooling Mode

    Heat Pump Cooling Mode Ambient Temperature °C Unit Size Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cap.ty input Cap.ty input Cap.ty input Cap.ty input Cap.ty input 22,6 21,4 20,5 19,4 18,1 23,4 22,1 21,2 20,1 18,9 23,8 22,5 21,7 20,6...
  • Page 13 Heat Pump Heating Mode Ambient Temperature °C Unit Size Heating Power Heating Power Heating Power Heating Power Heating Power Cap.ty input Cap.ty input Cap.ty input Cap.ty input Cap.ty input 23,0 24,4 26,1 26,9 27,4 22,5 23,8 25,3 26,1 27,1 M4AC080CR 22,0 23,3 24,8...
  • Page 14: Technical Data

    1.06 0.980 1.040 1.12 0.970 1.080 1.18 0.965 1.135 1.24 Water Pressure Drop And Flow Rate Water Flow Rate Water Pressure Drop MODEL m³/h M4AC080C 1.08 0.74 M4AC100C 1.31 0.82 M4AC120C 1.67 0.76 M4AC150C 0.74 Cooling 1.08 0.74 M4AC080CR Heating 1.14...
  • Page 15 Model: M4AC 080C(R)/100C(R)/120C(R)/150C(R) HP Gauge (SYS2) LP Gauge (SYS2) Cable Port(OUT) Cable Port (IN) Chilled Water Out Rc 1 1/4 Chilled Water In Rc 1 1/4 UNIT: mm Model M4AC080C(R) M4AC100C(R) M4AC120C(R) M4AC150C(R) Dimension 1500 1500 1800 1800 1150 1150...
  • Page 16 Model M4AC080C/100C Cooling only version 309 B/C – 03/03 A – page 16/28...
  • Page 17 Model M4AC080CR/100CR Heat Pump version 309 B/C – 03/03 A – page 17/28...
  • Page 18 Model M4AC120C/150C Cooling only version 309 B/C – 03/03 A – page 18/28...
  • Page 19 Model: M4AC120CR/150CR Heat Pump version 309 B/C – 03/03 A – page 19/28...
  • Page 20: Installation Notice

    Installation Installation Notice This equipment must be installed by your dealer or authorized McQuay qualified personnel, and the installation must satisfy all the following requirements. Location In order to achieve unit maximum capacity and long lifeoperation, the location selection should fulfill the following requirements: a) The location must be well ventilated, so that air can be drawn in and discharge out efficiently.
  • Page 21 For M4AC080C(R) to M4AC150C(R), if good ventilation cannot be guaranteed when unit being installed indoors, it is advisable to induce discharge air from air outlet to outdoors by installing duct which is as short as possible. e) Support unit base up to create a space above foundation for ensuring free water drainage, and the stable foundation with level surface must be sufficiently durable against the unit weight.
  • Page 22: Chilled Water Piping

    Delivery and Lifting When transporting the unit, it is advisable to use forklift or crane to do this work. Only the wooden skid base is allowed to be served as the weight-supporter. When hoisting, please keep the unit stable and without slope, meanwhile, be sure to avoid lifting cable contact with side heat exchanger, panel and unit’...
  • Page 23: Power Connection

    Both chilled water inlet and outlet port are external taper thread connections. When performing water pipe connection, use gripping pliers to fix the unit connections to avoid the reserved connections on unit being directly suffered from revolving torque when fastening. Chilled water in out pipe Slide panel C hi l l ed W at er I n or O ut P i pe...
  • Page 24: Electrical Data

    If auxiliary electric heater or auxiliary gas heater installation is required, please do installation after thoroughly reading corresponding manual. Carry out the electrical connection according to the diagram below so that achieve their automatic on/off governed by the unit controller. In addition, contact with local McQuay service representative for performing trail startup.
  • Page 25: Maintenance

    McQuay designers have given full consideration to make servicing convenient during unit development. After opening service panel, both servicing and maintenance can be easily carried out. Under normal environment, the only work needed is checking the return air way and cleaning the heat exchange surface regularly at month or season interval decided on operating condition.
  • Page 26: Schematic Diagrams

    When other code is displayed, please consult specialized personnel. See detailed indoor controller operation in corresponding instruction manual. Schematic Diagrams Cooling Only Version (M4AC080C/100C/120C/150C) C hi l l ed W at er I n C hi l l ed W at er O ut...
  • Page 27 Schematic Diagrams Heat Pump Version (M4AC080CR/100CR/120CR/150CR) C hi l l ed W at er C hi l l ed W at er O ut LEG E N D R ef r i ger ant Fl ow D i r ect i on W hen C ool i ng R ef r i ger ant Fl ow D i r ect i on W hen H eat i ng 4? C opper Tube Al um i ni um Fi n 1? C om pr essor...
  • Page 28 We reserve the right to make changes in design and construction at any time without notice, thus the cover and data are not binding McQuay Italia S.P.A. S.S. Nettunense, km 12+300 – 00040 Cecchina (Roma) Italia – Tel. (06) 937311 – Fax (06) 9374014 – E-mail: mcquay@mcquayitalia.com...

Table of Contents