McQuay MWSC 010 Series Manual page 20

Split water source heat pump and cooling only unit
Table of Contents

Advertisement

Model: MCC 030MR / MWSC 030BR
Indoor terminal
block
2) Electrical parameter
Indoor unit
Model
Outdoor unit
Power source
Cooling
Power input
(W)
Heating
Cooling
Running current
(A)
Heating
Section area(mm²)
Power supply
wire
Quantity
Section area (mm²)
Connecting
cable
Quantity
The wiring must be fi rmly connected.
ó
Electric wiring must not touch the refrigerant pipe, compressor and moving parts of the fan motor.
ó
The wiring between indoor unit and outdoor unit must be fi xed by clamp.
ó
All wiring between indoor unit and outdoor unit should be neoprene copper core, and section area of cable
ó
should be in accordance with above requirements.
The temperature sensor wire connecting outdoor unit with indoor unit
Connecting cable
The malfunction wire connecting outdoor unit with indoor unit
220-240V
Power supply cable
E
220-240V/1Ph/50Hz
N
L
MCC 010MR
MWSC 010BR
740
725
3.5
3.4
2.5
3
2.5
1.5
2
2
There must be a double pole switch
with minimum 3mm contact gap in the
installation circuit.
MCC 015MR
MCC 020MR
MWSC 015BR
MWSC 020BR
220V~/50Hz
1,170
1,635
1,100
1,470
5.5
7.6
5.2
6.8
2.5
2.5
3
3
2.5
1.5
2.5
2
2
2
Page 19
Outdoor terminal
block
F
MCC025MR
MCC 030MR
MWSC025BR
MWSC 030BR
1,950
1,840
9.0
8.6
2.5
3
1.5
2.5
1.5
2
2
2
2,350
2,360
10.8
10.8
2.5
3
2.5
1.5
2
3