External Dimensions, Installation and Connections

Dimensions
ME96SSHB-MB, ME96SSRB-MB
Terminal screw M3
Optional Plug-in Module :
ME-4210-SS96B,
ME-0040C-SS96, ME-0052-SS96
88.8
81.2
46.8
Mounting
1 Dimension of panel
Panel hole dimensions are as shown in the following figure.
It can be attached to a panel with thickness of 1.6 to 4.0 mm.
+ 0.5
92
0
3 Attachment
For attachment of the basic device into the panel hole, attach according to the following procedure.
qThe attachment lug is installed in two holes
of the top and bottom of the basic device.
4 Installing Optional Plug-in Module
When installing the optional plug-in module onto the basic device, install according to the following procedure.
qRemove the optional cover.
29
96.0
Optional Plug-in Module :
ME-0000BU-SS96
88.8
25.2
81.2
17.1
2 View Angle
The contrast of the display changes at view angle. Mount it at the position that is
easy to see.
wTighten the screws of the lug,
and fix onto the panel.
wAttach the optional
unit to the main unit.
ME96SSEB-MB
Terminal screw M3
Optional Plug-in Module :
ME-0000MT-SS96
88.8
25.2
81.2
17.1
ME96SSEB-MB
Viewing angle
10°
60°
(side view)
(overhead view)
To prevent damage to the panel and screws, do not overtighten
the screws.
Note
The recommended torque for this product is 0.3 N·m to 0.5 N·m
(about half the normal torque).
Tighten the two screws evenly.
Main unit mounting screws: M3
96.0
Optional Plug-in Module :
ME-0040MT2-SS96
88.8
81.2
25.2
17.1
ME96SSHB-MB/ME96SSRB-MB
Viewing angle
60°
60°
(side view)
(overhead view)
Fit the protruding part of the optional unit into
the slot in the main unit.
25.2
17.1