Mitsubishi Electric ME96 Super-S Series Manual page 20

Electronic multi-measuring instrument
Hide thumbs Also See for ME96 Super-S Series:

Advertisement

Operating Instructions
Set-up menu 3: Display settings (active energy, harmonics measurement, etc.)
Set-up menu
DISPLAY
SET
qActive/Reactive energy
measurement method
DISPLAY
SET
wHarmonic display
DISPLAY
SET
eUnbalance rate display
SET
Set-up menu
Set-up menu 6: Built-in logging settings
* Only for ME96SSHB-MB, ME96SSRB-MB, it is applicable.
Set-up menu
DISPLAY
SET
qOptional selection
DISPLAY
SET
wBuilt-in logging
Data clear
DISPLAY
SET
19
Adjust the set-up menu No. to "3".
qSet the display combination for imported/exported and lag/lead of active/reactive energy and
the measurement method for reactive energy.
Display combinations
Combinations
Wh
(set value)
Imported Exported
Lag
I
II
III
IV
Combinations I, II = >
Suitable for measurement in facilities not equipped with in-house generators,
and measuring reactive power of capacitor load, where power factor is around zero generally.
Combinations III, IV = > Suitable for measurements in facilities equipped with in-house generators.
<Example display screens>
Combination I
Combination II
: Imported
: Exported
wSet whether to display the harmonic measured value.
on
oFF
(Display)
(Not display)
When you set to "on (Display)", harmonic measured values are displayed on
the additional screen of display pattern.
eSet whether to display unbalance rate.
on
oFF
(Display)
(Not display)
When you set to "on (Display)", voltage/current unbalance rate
can be displayed on the additional screen of display pattern.
Note. For 1-phase 2-wire system, this setting is skipped.
Select another set-up menu or end set-up
‡To continue to set-up
Select the menu
No. using the
or
button.
Adjust the set-up menu No. to "6". (See the drawing on the right)
Select analog output, built-in logging, or optional logging.
Ao
PLUG
buiLt
(Analog output) (Optional logging) (Built-in logging)
The explanation here is about built-in logging settings.
For the analog output settings, refer to Set-up menu 6: Analog output setting.
For the optional logging settings, refer to Set-up menu 6: Logging setting.
Note. When ME-4210-SS96B or ME-0000BU-SS96 of optional module is not installed, this setting is skipped.
Clears logging data stored in the main body
no
yES
(Not clear)
(Clear)
When yES (Clear) is selected above, the confirmation screen appears to ask whether or not to clear data.
no
yES
(Not clear)
(Clear)
varh
Imported
Exported
Lead
Lag
Lead
2 Quadrants Measurement
4 Quadrants Measurement
Combination III
Combination IV
: varh (lead)
‡To finish set-up
Press the
or
to display the End screen,
then press the
SET
to save settings.
Reactive energy
measurement
method
: varh (lag)
w
e
button
button