Download Print this page

Mitsubishi Electric ME96 Super-S Series Manual page 12

Electronic multi-measuring instrument
Hide thumbs Also See for ME96 Super-S Series:

Advertisement

Specifications
‡ME96SSEB-MB
Model name
Phase wire system
Rating
Item
Current (A)
Current demand (DA)
Voltage (V)
Active power (W)
Reactive power (var)
Apparent power (VA)
Power factor (PF)
Measuring
element
Frequency (Hz)
Active energy (Wh)
Reactive energy (varh)
Apparent energy (VAh)
Harmonic current (HI)
Harmonic voltage (HV)
Operating time (h)
Measuring
method
The number of display digits or
Display
The number of segments
Display update time interval
Communication
Connectable Optional Plug-in Module
Power interruption backup
Voltage circuit
VA consumption
Current circuit
Auxiliary power circuit
Auxiliary power
Weight
Dimensions
Mounting method
Operating temperature/humidity
Storage temperature/ humidity
Note 1. The class value is a percentage of rated value (100%).
Note 2. For harmonics measurement where distortion ratio (content rate) is 100% or more, it can exceed ±2.0%.
Note 3. When there is no voltage input, harmonic current cannot be measured.
11
Current
Voltage
Frequency
Instantaneous value
Demand value
Display type
Digital section
3-phase 4-wire, 3-phase 3-wire (3CT, 2CT), 1-phase 3-wire, 1-phase 2-wire (common use)
5 A AC, 1 A AC (common use)
3-phase 4-wire: max 277/480 V AC
3-phase 3-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC
1-phase 3-wire: max 220/440 V AC
1-phase 2-wire: (DELTA) max 220 V AC, (STAR) max 440 V AC
50/60 Hz (common use)
Measuring Item
A1, A2, A3, AN, A
AVG
DA1, DA2, DA3, DAN, DA
AVG
V12, V23, V31, V
(L-L), V1N, V2N, V3N, V
AVG
W1, W2, W3, ∑ W
var1, var2,var3, ∑ var
VA1, VA2, VA3, ∑ VA
PF1, PF2, PF3, ∑ PF
Hz
Imported, Exported
Imported lag, Imported lead, Exported lag, Exported lead
Imported + Exported
Total
Total
Operating time 1, Operating time 2
A, V: RMS value calculation; W, var, VA, Wh, varh, VAh: Digital multiplication;
PF: Power ratio calculation; Hz: Zero-cross; HI, HV: FFT
DA: Thermal type calculation
LCD with LED backlight
First to Third line display: 4 digits, Fourth line display: 6 digits
A, DA, V, W, var, VA, PF: 4 digits; Hz: 3 digits;
Wh, varh, VAh: 9 digits (6-digit or 12-digit is also available.);
Harmonic distortion ratio/content rate: 4 digits; Harmonic RMS value: 4 digits;
Operating time: 6 digits
0.5 s, 1 s (selectable)
MODBUS RTU communication
Cannot connect optional module
Use of nonvolatile memory (Items: settings, MAX/MIN value, active energy, reactive energy, apparent
energy, operating time)
Each phase: 0.1 VA (at 110 V AC), 0.2 VA (at 220 V AC), 0.4 VA (at 440 V AC)
Each phase: 0.1 VA
4 VA (at 110 V AC), 5 VA (at 220 V AC), 3 W (at 100 V DC)
100 V to 240 V AC (±15%), 100 V to 240 V DC (-30% +15%)
0.3 kg
96 (H) × 96 (W) × 36 (D) mm
Embedded
-5°C to +55°C (Daily average temperature: 35°C or less), 0% to 85% RH, Non condensing
-25°C to +75°C (Daily average temperature: 35°C or less), 0% to 85% RH, Non condensing
ME96SSEB-MB
(L-N)
AVG
±0.5%
±0.5%
±0.2%
Class 0.5S (IEC62053-22)
Class 1S (IEC62053-24)
±2.0%
±2.0%
(Reference)
Class

Hide quick links:

Advertisement

loading