Download Print this page

Mitsubishi Electric ME96 Super-S Series Manual page 17

Electronic multi-measuring instrument
Hide thumbs Also See for ME96 Super-S Series:

Advertisement

(2) For measurement with VT
eVT/Direct voltage
<Secondary voltage settings>
DISPLAY
SET
<Set primary voltage>
The setting ranges from 60 V to 750,000 V (setting unit: V)
Factory default settings
rCT current
rSet CT.
Set the primary and secondary currents of the CT to be combined.
<Set secondary current>
<Set primary current>
DISPLAY
SET
The setting ranges from 1.0 A to 30,000.0 A (setting unit: A)
Factory default setting: 5.0 A
tSet frequency.
tFrequency
Notes1. Analog output scale will also change.
DISPLAY
SET
yRolling demand time
ySet the rolling demand interval time limit
limit
(1) Interval time limit
(2) Sub-interval time limit
DISPLAY
SET
uCurrent demand time
uSet the current demand time limit.
limit
SET
Set-up menu
Select another set-up menu or finish set-up.
‡To continue to set-up
Select the menu No.
using the
Set-up menu 2: MODBUS RTU Communication settings
(When ME-0040C-SS96, ME-0000MT-SS96 and ME-0040MT2-SS96 are not installed)
Set-up menu
Adjust the set-up menu No. to "2".
DISPLAY
SET
qMODBUS RTU
qSet MODBUS RTU communication address
communication address
Possible address settings: 1-255
DISPLAY
SET
wSet the MODBUS RTU communication baud rate.
wMODBUS RTU
Baud rate
DISPLAY
SET
(a) 3-phase 4-wire setting (phase voltage)
63.5 V
100 V
110 V
(b) 3-phase 3-wire (2CT, 3CT) or 1-phase 2-wire setting (line voltage)
100 V
110 V
220 V
3-phase 4-wire: 200 V (phase voltage)
3-phase 3-wire; 1-phase 2-wire: 10,000 V (line voltage)
1 A
5 A
50 Hz
60 Hz
(Only ME96SSHB-MB and
Setting range
Setting interval
1 - 15 - 60 (min)
1 min
Setting range
Setting interval
1 - 60 (min)
1 min
0 s
40 s
3 min
7 min
10 s
50 s
4 min
8 min
20 s
1 min
5 min
9 min
30 s
2 min
6 min
10 min
or
button.
2400 bps
4800 bps
9600 bps
19.2 kbps
38.4 kbps
115 V
120 V
t
ME96SSRB-MB).
u
15 min
20 min
25 min
30 min
‡To finish set-up
Press the
or
button
to display the End screen,
then press the
button
SET
to save the settings.
q
e(2)
r
y
w
16