SMC Networks ISE35 Operation Manual page 33

Digital pressure switch
Hide thumbs Also See for ISE35:
Table of Contents

Advertisement

○Error indication function
This function is to display error location and content when a problem or an error occurs.
Error Name
Error Display
Over current
Error
Residual
pressure
Error
Pressurizing
Error
System Error
If the error can not be reset after the above measures are taken, then please contact SMC.
Error Type
A load current of switch output is 80 mA
or more.
During zero clear operation, pressure
over 10%F.S. is applied. After 3 s, the
mode will reset to the measurement
mode. ±1 digit of the zero clear range
varies with individual product
differences.
Pressure has exceeded the upper limit
of the set pressure range.
Pressure has exceeded the lower limit
of the set pressure range.
Displayed in the case of an internal data
error.
-32-
Troubleshooting Method
Turn the power off and remove the
output factor for the over current.
Then turn the power on.
Perform zero clear operation again after
restoring the applied pressure to an
atmospheric pressure condition.
Reset applied pressure to a level within
the set pressure range.
Turn the power off and turn it on again.
If resetting fails, an investigation by
SMC Corporation will be required.
No.PS※※-OMJ0004-E