SMC Networks ISE35 Operation Manual page 31

Digital pressure switch
Hide thumbs Also See for ISE35:
Table of Contents

Advertisement

Reference
Problem
No.
●The display
turns off.
●A part of the
8
display
misses.
The display is
9
flashing.
The display is
10
inverted.
The indication
accuracy of
the pressure
11
does not
satisfy the
specifications.
Possible cause
Investigation method
Improper
Confirm that the power supply voltage
power supply
is in the range of 12 to 24 VDC10%.
Power saving
Check if the power saving mode is
mode
selected.
Check the wiring for the power supply.
Confirm that the brown and blue wires
Incorrect wiring
are connected to DC(+) and DC(-)
respectively, and that the output line
has not come off (contact failure).
Product failure
Peak/bottom
Check if the peak indication mode or
indication
bottom indication mode has been
mode
selected.
1. Check the wiring to the power
supply.
Wiring failure
2. Check if bending stress is being
applied to part of the lead wire.
Selection of
unsuitable
model
Check the part number for the
(Selection of
electrical entry.
wrong
electrical entry)
Change of
indication
Check the selected indication mode.
mode
Check for the intrusion and
Intrusion of
attachment of foreign matter into the
foreign matter
pressure port.
Check the air leakage from the
Air leakage
mounted part.
(Presence of the O-ring)
Confirm that the specified accuracy is
Insufficient
satisfied 20 min. after the power
warming-up
supply is turned on.
Product failure
-30-
Countermeasure
Supply a power supply voltage
of 12 to 24 VDC10%.
Set functions.
Correct the wiring.
Replace the product.
Release the peak/bottom
indication mode.
1. Correct the wiring.
2. Modify the wiring (bending
radius and stress).
Review the selected model.
Change the indication mode.
Install a 5μm filter to prevent
the intrusion and attachment of
the foreign matter. Also,
exhaust the filter periodically to
prevent drainage deposits.
Rework the assembly process
of the regulator.
If the regulator is tightened at a
torque over the specified range,
its mounting screw could break.
Also, remount the O-ring.
The figures in the display and
output drift when the power
supply is turned on. If fine
pressure needs to be detected,
wait approximate 20 to 30 min.
after turning on the power
supply to allow it to warm up.
Replace the product.
No.PS※※-OMJ0004-E