3.3 Technical Data
2)
Safety function
Stroke
Positioning time
Positioning force
Voltage supply
Power consumption
Input signal
Output signal
Behavior in case of a
drop-out
Type of protection
acc. to EN 60529
Safety class DIN VDE 0106
Ambient operation
temperature
Ambient storage and
transportation
temperature
End position switch-off
Additional Equipment (cannot be added later)
End switches
(only design AMV210, 213)
1)
Stem remains in last position
2)
Stem extends
AMV210
-
mm
s/mm
N
V
230 V
VA
Three-position
230 V, 50/60 Hz
1)
IP 54 if installed in a vertical upright position,
°C
° C
(2 pieces)
voltage-free, two-way switch, max. 250 V AC or
DC, 2 A resistive load, 1 A inductive load
AMV213
yes
15
12
300
50/
,
+10 % -15 %
60 Hz
8
step signal
–
2)
other installation positions: IP 52
II
-10 to +50
-10 to +70
Switch-off dependent on torque
Device Description
AME210
AME213
-
yes
24 V
,
+10 % -15 %
50/60 Hz
0(4)–20 mA
0(2)–10 V
0(2)–10 V
1)
2)
27