TX Matrix Plus Router Quick Start
Step 3: Install the TX Matrix Plus Router Using a Mechanical Lift
Remove TX Matrix Plus Components
12
Table 5: Mounting Hole Locations for Installing a TX Matrix Plus
Open-Frame Rack Shelf
Hole
Distance Above U Division
42
24.25 in. (61.6 cm)
39
22.5 in. (57.2 cm)
36
20.75 in. (52.7 cm)
33
19.0 in. (48.3 cm)
30
17.25 in. (43.8 cm)
27
15.5 in. (39.4 cm)
24
13.75 in. (34.9 cm)
21
12.0 in. (30.5 cm)
18
10.25 in. (26.0 cm)
15
8.5 in. (21.6 cm)
12
6.75 in. (17.1 cm)
9
5.0 in. (12.7 cm)
6
3.25 in. (3.8 cm)
1.
Remove TX Matrix Plus Components on page 12
Install the TX Matrix Plus Router Using a Lift on page 14
2.
Reinstall TX Matrix Plus Components on page 21
3.
Before lifting the TX Matrix Plus router, you must remove the following components:
Input power trays
Power supplies
TXP-CBs and Routing Engines
Front and rear fan trays
TXP-F13 SIBs or TXP-F13-3D SIBs
TXP-F2 SIBs or TXP-F2-3D SIBs
Open-Frame MountingShelf
13.86 U
X
12.86 U
X
11.86 U
X
10.86 U
X
9.86 U
X
8.86 U
X
7.86 U
X
6.86 U
X
5.86 U
X
4.86 U
X
3.86 U
X
2.86 U
X
1.86 U
X