4004_RevDB.fm Page 17 Wednesday, November 23, 2011 3:06 PM
Quick Installation Guide
00825-0100-4004, Rev DB
December 2011
Hazardous Location Certifications
Rosemount 8800D
North American Certifications
Factory Mutual (FM)
E5
Explosion-Proof for Class I, Division 1, Groups B, C, and D;
Dust-ignition proof for Class II/III, Division 1, Groups E, F, and G;
Temperature Code T6 (-50 °C T
Factory Sealed
Enclosure Type 4X
I5
Intrinsically safe for use in Class I, II, III Division 1, Groups A, B, C, D, E, F, G;
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
NIFW (Non-incendive Field Wiring) when installed per Rosemount Drawing
08800-0116
Temperature Code T4 (-50 °C  T
Temperature Code T4 (-50 °C  T
IE
FISCO for Class I, Division 1, Groups A, B, C, and D.
FNICO for Class 1 Division 2, Groups A, B, C, and D.
Temperature Code T4 (-50 °C  T
when installed per Rosemount control drawing 08800-0116.
Enclosure Type 4X
K5
E5 and I5 Combination
Special conditions for safe use (x)
When fitted with 90V transient suppresors (T1 Option), the equipment is not capable of
passing the 500V insulation test. This must be taken into account upon installation.
The enclosure may be made of an aluminum alloy, and given a protective polyurethane
paint finish: care should be taken to protect the housing from impact or abrasion.

Canadian Standards Association (CSA)

E6
Explosion-Proof for Class I, Division 1, Groups B, C, and D;
Dust-ignition proof for Class II and Class III, Division 1, Groups E, F, and G;
Class I, Zone 1, Ex d[ia] IIC CSA 06.1674267
Temperature Code T6 (-50 °C  T
Factory Sealed
Single Seal.
Enclosure Type 4X
I6
Intrinsically safe for use in Class I, II, III Division 1, Groups A, B, C, D, E, F, G;
Non-incendive for Class I, Division 2, Groups A, B, C and D
Temperature Code T4 (-50 °C  T
Temperature Code T4 (-50 °C  T
Single Seal.
Enclosure Type 4X
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Rosemount 8800D
70 °C)
a
 70 °C) 4-20 mA HART
a
 60 °C) Fieldbus
a
 60 °C)
a
 70 °C)
a
 70 °C) 4-20 mA HART
a
 60 °C) Fieldbus
a
17

Advertisement

Table of Contents
loading

Table of Contents