Settings - IBA ibaClock Manual

Time synchronization module for ibapda systems
Table of Contents

Advertisement

Note
Ask the network administrator for a suitable IP address for your network.
The following IP addresses are not admitted:
0.0.0.0, broadcast: 255.255.255.255 and localhost addresses (also known as loopback
addresses): 127.0.0.0 to 127.255.255.255 as well as the multicast addresses 224.0.0.0
to 239.255.255.255 (224.0.0.0/4).
For the IP address, the "standard IPv4 dotted-decimal format" without leading zeros is
used. Eventually inserted leading zeros will be eliminated automatically at the takeover
of the IP addresses.
9.3.4

Settings

This page is only accessible after the login over the user "admin".
Figure 7: Web interface time source / time distribution
(1) The "Time Source" can be determined here.
<GPS>, <RTC>, <IRIG> and <PTP> are available.
If a GPS antenna has not yet been installed during commissioning, the time can be
specified by RTC in order to synchronize the connected devices.
(2) The item „Time Distribution" provides the distribution services, which can be individ-
ually enabled or disabled. However, the distribution via fiber optic is always enabled.
If <PTP> is activated as time source, the "Time Distribution" for PTP is deactivated.
28
Manual
Issue 1.4
ibaClock

Advertisement

Table of Contents
loading

Table of Contents