Technical Data; Main Data - IBA ibaClock Manual

Time synchronization module for ibapda systems
Table of Contents

Advertisement

11

Technical data

11.1

Main data

Manufacturer
Order number
Description
Time sources
GPS
IRIG-B
IEEE 1588
Time server function
ibaNet
IEEE 1588
NTP
Time & Daytime
*
DCF77
Alarm
Alarm
Interfaces / features
*
For future firmware versions
42
Manual
iba AG, Germany
10.160000
Universal time server
Supported GPS antenna: Smart antenna Trimble
Acutime GG / Acutime 360; power supply via
ibaClock
Antenna precision: 15 ns (static)
Cable length: up to 400 m
Control accuracy of the internal PLL:
(typ.) < ±150 ns of the absolute GPS PPS signal
Time stability in case of GPS signal loss: < 0.15
ppm after min. 10 minutes of receiving GPS
Plug connector: BNC, 50 Ω
Supported telegrams:
B004, B124, B005, B125, B006, B126,
B007, B127
IEEE1344 / IEEE C37.118
AFNOR NF S87-500
(Firmware: v01.03.001 and higher)
PTP (Precision Time Protocol), hardware based
Time synchronization of ibaPDA systems via fiber
optics
PTP (Precision Time Protocol), hardware based
Synchronization over network via NTP
According to RFC 868 and RFC 867
Optional output of the DCF77 time code via semi-
conductor relay output
Semiconductor relay output, switching current up to
200 mA, open in de-energized state
Issue 1.4
ibaClock

Advertisement

Table of Contents
loading

Table of Contents