6. Tighten cable glands well to obtain optimum sealing. The cable entry gasket must obtain
firm contact with the cable.
7. Remount terminal box lid.
Note
Tightening torque
Tighten the bolts with 0.5 Nm.
5.2

Installation check

The meter is now ready to go into normal operation - for commissioning and setting of
parameters refer to the relevant transmitter manual.
SITRANS FM MAG 5100 W
Operating Instructions, 01/2020, A5E03063678-AC
CAUTION
Unscreened cable ends
Keep unscreened cable ends as short as possible.
CAUTION
Prevent interference
Separate electrode and coil cables to prevent interference.
WARNING
Use in hazardous area
Connect mains protective earth to the PE terminal in accordance with the above diagram
in order to obtain potential equalization.
Connecting
5.2 Installation check