Cable Data - Siemens SITRANS F Series Operating Instructions Manual

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

8.2

Cable data

Description
Cable for standard electrode or coil
Electrode cable, double shielded
Cable kit with standard coil cable and electrode cable double
shielded (also available as low noise cable for MAG 1100 sensor)
Standard applications
Table 8-6
Basic data
Max. cable loop resistance
Cable glands on sensor and
transmitter
Special applications, for example low conductivity or electrical noise
Table 8-7
Basic data
Ambient temperature
SITRANS FM MAG 5100 W
Operating Instructions, 01/2020, A5E03063678-AC
Technical data, standard application cables
No. of conductors
Min. sqr. area
Shield
Max. capacitance
Media temperature:
< 100 °C (212 °F)
> 200 °C (392 °F)
M20x1.5 gland - Cable ø 5 to 13 mm (0.20 to 0.51 inches)
½ NPT gland - cable ø 5 to 9 mm (0.20 to 0.35 inches)
Technical data, special application cables
No. of conductors
Sqr. area
Shield
Color code
Outside color
Ext. diameter
Conductor
Isolation material
Flexible installation
Non-flexible installtaion
Coil cable
2
0.5 mm
2
Yes
N/A
40 Ω
6 Ω
Coil cable
Special electrode cable
3
1.5 mm
2
Yes
Brown, blue, black
Grey
7.8 mm
Flexible CU
PVC
-5 to +70°C
(23 to 158°F)
-30 to +70°C
(-22 to 158°F)
Technical data
8.2 Cable data
Standard electrode
cable
3
0.2 mm
2
Yes
350 pF/m
N/A
N/A
3
0.25 mm
2
Double
Brown, blue, black
Grey
8.1 mm
Flexible CU
PVC
-5 to +70°C
(23 to 158°F)
-30 to +70°C
(-22 to 158°F)
53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fm mag 5100 w7me6527me658