Depending on the prescribed setpoint, the sine oscillation of the mains voltage is
gated using a larger or smaller control angle α. This operating mode is characterized
by high control dynamics.
Figure 5‑42. VAR waveform

STARTING MODES

The Thyro-PX power controller has enhanced starting modes that are used with
special loads. These modes are used when the unit is started or restarted, and the
restart behavior can be configured.

RAMP Starting Mode

This starting mode begins with a specially configured, one-time block, normally in
the form of a ramp (default). It is used to symmetrize transformers during restart. It
can be configured in the same manner as the standard TAKT. See also
Modes"
on page 5‑42.

MOSI Starting Mode

The MOSI starting mode is used for sensitive heating materials with a high R
R
ratio, such as molybdenum disilicide. The power controller limits the maximum
cold
current to the load during the low-resistance heating-up phase, and then automatically
switches to the set operating mode.

SETPOINT CONTROL

The setpoint control characteristic of the Thyro-PX power controller is easily adapted
for the control output signal of the upstream process controller or automation system.
All typical control voltage and control current signals can be used. Inverted operation
(ending value is smaller than the starting value in voltage or current) is also
supported.
The effective setpoint is the total setpoint. It is formed by adding the three setpoints
as shown in
57010148-00G
Figure
5‑43.
Installation, Setup, and Operation
®
Thyro-PX
Power Controller
"Operating
warm
/
5‑43