Table 3-5. Type Voltage 500 Volts - Advanced Energy Thyro-PX Series User Manual

Power controller
Hide thumbs Also See for Thyro-PX Series:
Table of Contents

Advertisement

®
Advanced Energy
Table 3‑4. Electrical specifications (Continued)
Description
Precision
Limitations
Relays
Table 3‑5. Type voltage 500 volts
Model
Type Power
Type Current
(A)
(kVA)
Thyro-PX 1PX
16 H
8
37 H
18
75 H
38
110 H
55
130 H
65
170 H
85
280 HF
140
350 HF
175
495 HF
248
650 HF
325
780 HF
390
1000 HF
500
1500 HF
750
2100 HF
1050
57010148-00G
U-control: Better than ± 0.5%
I-control: Better than ± 0.5%
P-control: Better than ± 1%
All specifications are relating to the respective final value.
Voltage limitation U
rms
Current limitation I
= default setting
rms
Effective power limitation P
Peak current limitation, MOSI starting mode
Rated current: 6 A
Rated voltage: 277 VAC, 24 VDC
General use
Contact material: AgNi+Au
Dissipation
Transformer
(W)
71
400/1
105
100/1
130
100/1
175
100/1
190
150/1
220
200/1
365
300/1
477
500/1
595
500/1
750
700/1
1180
1000/1
1450
1000/1
1775
1500/1
2600
2000/1
Specifications
Thyro-PX
Specification
Current
Burden
T1
R (Ω)
27.4
2.7
1.30
0.91
1.10
1.10
1.00
1.30
1.00
1.00
1.00
1.00
1.00
0.91
®
Power Controller
Fuse F1
(A)
50
50
100
180
200
315
350
500
630
900
2x700
2x1000
4x900
4x1000
3‑5