Table 5-2. Terminal Screw Size; Table 5-3. Terminal Screw Torque - Advanced Energy Thyro-PX Series User Manual

Power controller
Hide thumbs Also See for Thyro-PX Series:
Table of Contents

Advertisement

®
Advanced Energy
a. Use the screw size specified in
b. Tighten to the torque specified in
5. For 1PX and 2PX units, connect the reference phase to A1 X1.3.
6. Connect a current-limited external power source to the auxiliary power input
connector on the bottom of the unit. Connect either:
◦ 90 VAC to 265 VAC (230 V, 150 mA) to connector X1
◦ 24 VDC, 1 A to connector X3
Use the included plug-in, screw-terminal block to make this connection. Follow
the torque recommendation for M2 terminal screws.
7. For HF units, connect the 230 VAC (or 115 VAC special option) fan power
supply to connector X7.
Use the included plug-in, screw-terminal block to make this connection. Follow
the torque recommendation for M2 terminal screws.
8. Reinstall the plastic cover(s) removed for step 1.
Table 5‑2. Terminal screw size
37 H, 75 H
80 H
110 H
130 H, 170 H
200 HF, 280 HF, 300 HF 495 HF, 500 HF, 650 HF
780 HF, 1000 HF, 1400 HF, 1500 HF, 1700 HF, 1850 HF,
2000 HF, 2100 HF, 2200 HF, 2400 HF, 2600 HF,
2750 HF, 2900 HF
Table 5‑3. Terminal screw torque
Screw
Minimum NM
(Pound-Inches)
M2
0.2 (1.9)
M4
1.0 (8.9)
M6
3.0 (26.1)
M8
11.5 (101.8)
M10
22.0 (194.7)
M12
38.0 (336.3)
57010148-00G
Model
Rated NM
(Pound-Inches)
0.25 (2.2)
1.3 (11.5)
4.4 (38.9)
17.0 (150.5)
33.0 (292.1)
56.0 (495.6)
Installation, Setup, and Operation
Thyro-PX
Table
5‑2.
Table
5‑3.
Connector
Screw
M6
M8
M6
M8
M10
M12
Torque
0.3 (2.5)
1.7 (15.0)
5.9 (52.2)
22.5 (199.1)
44.0 (389.4)
75.0 (663.8)
®
Power Controller
Protective
Earth Screw
M6
M10
M6
M10
M10
M12
Maximum NM
(Pound-Inches)
5‑32

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thyro-px 1pxThyro-px 2pxThyro-px 3px