Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 60

With vav-rtu open controller
Table of Contents

Advertisement

1 Default to meet California Title 24 requirements is 45°F
2 Do Not Use
3 Input Switch Configuration must be set for each Input Function
4 This input will only be shown if Service Configuration>Heat Type is set to Electric. For gas units (Service Configuration> Heat Type
set to 1 = Gas (48 series units) this input is automatically set to 7 = IGC Override
5 This input will only be shown if Input Configuration>Input 2 Function is set to 3 = Space RH Sensor and there is a valid Space Rela-
tive Humidity value on J4 -2&3
6 This input will only be shown if Input Configuration>Input 2 Function is set to 2 = IAQ Sensor and there is a valid Indoor Air Quality
CO
Sensor value on J4 -2&3
2
7 This input will only be shown if Input Configuration>Input 2 Function is set to 2 = OAQ Sensor, there is a valid Indoor Air Quality CO
Sensor value on J4 -2&3, and Service Configuration>DCV Control is set to Enable at one of the VAV Zone controllers which has Ser-
vice Configuration>Hardwired Sensor set to CO
8 This setpoint will only be shown if Service Configuration>SA Tempering is set to Enable
9 Compressor Stages default is Three Stages and cannot be changed
10 Economizer Exist default is Yes and cannot be changed
11 This configuration will only be shown if Input Configuration>Input 2 Function is set to 2 = IAQ Sensor
12 This configuration will only be shown if Input Configuration>Input 2 Function is set to 4 = OAQ Sensor
13 If using a Carrier Comfort Network
Instance can be 1, 2, 3, or 4, depending on the number of air sources used in the system.
© 2020 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480277-01
Sensor with a valid value on J4 - RH&Gnd
2
(CCN) and BACnet System (i.e., Carrier CCN Air Terminal to BACnet Air Source), the Application
®
Printed in U.S.A.
Form 48-50LCB-7-26-02T Rev. A
Pg CL-4
3-2020 Replaces: 48-50LCB-7-26-01T
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

50lcb0748lcb2650lcb26