Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 48

With vav-rtu open controller
Table of Contents

Advertisement

Point Name
Active Cooling Stages
Active Heat Stages
Air Source Mode
Air Source Outdoor Air Temp
Air Source Static Pressure
Air Source Supply Air Temp
Airside Linkage
Analog Input Configuration
BAS On / Off
Compressor 1 Relay State
Compressor 1 Runtime
Compressor 1 Runtime
Compressor 1 Service Alarm Timer
Compressor 1 Test
Compressor 2 Relay State
Compressor 2 Runtime
Compressor 2 Runtime
Compressor 2 Service Alarm Timer
Compressor 2 Test
Compressor 3 Relay State
Compressor Safety Status
Compressor Status
Continuous Occupied Exhaust
Controlling Temperature
Cooling Lockout Temperature
Ctrl Temp Sensor Failure
Ctrl Temp Source
Current Static Pressure Setpoint
DCV Control
DCV Max Ctrl Setpoint
DCV Max Vent Damper Pos
Door Contact Status
Economizer
Economizer Exists (required)
Economizer High OAT Lockout Temp
Economizer Operation
Economizer Output
Economizer Test
Effective Cool Setpoint
Effective Heat Setpoint
Enthalpy (BACnet)
Enthalpy Status
Equipment Status
Factory Test Analog 1 Control
Factory Test Analog 2 Control
Factory Test Relay 1 Control
Factory Test Relay 2 Control
APPENDIX D — BACnet POINTS LIST
Table C — VAV-RTU Open Protocol Maps
Point
Units
Access
R
no units
R
no units
R
1=Off
2=Warmup
3=Heating
4=Cooling
5=Freecool
6=Pressure
7=Evac
8=Vent
R
°F
R
in H2O
R
°F
R
R
R/W
1=Inactive
2=Occupied
3=Unoccupied
R
R
R
hr
R/W
hr
R/W
R
R
R
hr
R/W
hr
R/W
R
R
R
R/W
R
°F
R/W
°F
R
R
1=Sensor Failure
2=Space
3=Return Air
4=Linkage Zone
5=Locked Value
R
in H2O
R/W
R/W
ppm
R/W
%Open
R
R
1=Normal
2=Failed to Fully Open
3=Failed to Open
4=Failed to Close
5=Stuck Open
R/W
R/W
°F
R
R
%Open
R/W
%Open
R
°F
R
°F
R/W
R
R
1=Disabled
2=Test
3=Run
R/W
%
R/W
%
R/W
R/W
48
Default
BACnet Point Name
Value
et_comp_run
heat_run
link_ahu_mode
link_ahu_oat
link_sp
link_sat
air_linkage_fail
ai_cfg_alarm
1
keypad_ovrde
comp_1
comp1_rntm_alarm
comp1_rntm
0
comp1_service_hrs
Inactive (0)
comp1_test
comp_2
comp2_rntm_alarm
comp2_rntm
0
comp2_service_hrs
Inactive (0)
comp2_test
comp_3
comp_status
comp_alarm
Inactive (0)
occ_exh
ctrl_temp
45
oat_cl_lockout
ctrl_temp_fail
ctrl_temp_src
sa_static_stpt_value
Inactive (0)
dcv_enable
1100
iaq_stpt_max
50
iaq_dpr_max
door_contact_status
econ_fdd_result
Active (1)
econ_exist
75
oat_ec_lockout
econ_opr
econ_output
0
econ_test
eff_cl_stpt
eff_ht_stpt
Active (1)
oae
enthalpy_status
mode_status
0
ao1_fac_test
0
ao2_fac_test
Inactive (0)
relay1_fac_test
Inactive (0)
relay2_fac_test
BACnet
Object ID
AV:2020
AV:2003
MSV:2005
AV:2609
AV:2610
AV:2608
BV:7030
BV:7026
MSV:1001
BV:2005
BV:7014
AV:2017
AV:83006
BV:81005
BV:2004
BV:7015
AV:2018
AV:83007
BV:81004
BV:2007
BV:1008
BV:7013
BV:9002
AV:2035
AV:9002
BV:7067
MSV:2013
AV:3031
BV:1027
AV:3013
AV:9011
BV:1010
MSV:2011
BV:99001
AV:9008
BV:7054
AV:2022
AV:81001
AV:3005
AV:3006
BV:1901
BV:1002
MSV:2001
AV:91001
AV:91002
BV:91001
BV:91002