Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 37

With vav-rtu open controller
Table of Contents

Advertisement

Access Level
Equipment Touch or
3 = ADMIN
System Touch Menu
2 = USER
1 = None
Property Pages>
3
Configuration>
Unit Configuration>
Input Configuration
3
3
3
3
3
3
3
3
3
3
3
3
Property Pages>
3
Configuration>
3
Unit Configuration>
Sensor Calibration
3
3
3
3
3
3
3
3
3
3
APPENDIX A — USER INTERFACE MENUS (CONT)
Table A — User Interface Menus (cont)
POINT NAME
INPUT CONFIGURATION
Input 2 Function
Input 3 Function
Input 3 Switch
Configuration
8
Input 5 Function
Input 5 Switch
Configuration
Input 8 Function
8
Input 8 Switch
Configuration
8
Input 9 Function
9
Input 9 Switch
Configuration
8, 9
ZS Sensor Binder Alarm ALARM/Normal
ZS Space Temp
ZS Space Humidity
ZS Space CO2
SENSOR CALIBRATION
Space Temp
Space RH
3
Space AQ
4
Outdoor AQ
5
Static Pressure
Static Pressure
Calibration
Supply Air Temperature
Supply Air Temp
Calibration
Return Air Temperature
Return Air Temp
Calibration
Outdoor Air Temperature -56 - 245°F
Outdoor Air Temp
Calibration
RANGE
1 = No Sensor
No Sensor
2 = IAQ Sensor
3 = Space RH Sensor
4 = OAQ Sensor
1 = No Function
No Function
2 = Compressor Safety
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
7
6 = Door Contact
7
1 = NO (Normally Open)
NO
2 = NC (Normally
Closed)
1 = No Function
Fire Shutdown
2 = Fire Shutdown
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
7
6 = Door Contact7
1 = NO (Normally Open)
NO
2 = NC (Normally
Closed)
1 = No Function
No Function
2 = Enthalpy Switch
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
7
6 = Door Contact
7
1 = NO (Normally Open)
NO
2 = NC (Normally
Closed)
1 = No Function
No Function
2 = Humidistat
7
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
7
6 = Door Contact
7
7 = IGC Override
NO (Normally Open)
NO
NC (Normally Closed)
°F
%rh
ppm
°F
%rh
ppm
ppm
0.00 - 2.50 "wc
-0.2 - 0.20 "wc
0
-56 - 245°F
-9.9 - 10∆°F
0∆
-56 - 245°F
-9.9 - 10∆°F
0∆
-9.9 - 10∆°F
0∆
37
DEFAULT
Field Assistant Menu
Properties>
Control Program>
Configuration>
Unit Configuration>
Input Configuration
Properties>
Control Program>
Configuration>
Unit Configuration>
Sensor Calibration