APPENDIX B — VAV ZONE AIRSIDE LINKAGE CONFIGURATION
Access Level
Equipment Touch or
3 = ADMIN
System Touch Menu
2 = USER
1 = None
Air Terminal
N/A
Properties>Startup
Wizard>
Airside Linkage
Configuration
N/A
N/A
3
3
N/A
3
N/A
3
3
N/A
N/A
N/A
3
3
Air Terminal
3
Properties>
Startup Wizard>
3
Airside Linkage
Configuration>
3
Air Source
Configuration
Table B — VAV Zone Airside Linkage Configuration
POINT NAME
AIRSIDE LINKAGE
Linkage CollectorIf
1 to 64
Master zone, set Number
of Providers to the total #
of controllers that will
report to the Master,
including the master
For a slave zone the # of
providers is 1
Linkage Provider If
Network Number: 0 to
Master zone, set MS/TP
65,535
network number and
MAC Address: 0 to 127
MAC address of the RTU
(air source) with the VAV-
RTU Open controller
For a slave zone leave at
zero
Airside Linkage Status
Active/Not Active
Linkage Zone Type
Slave
VVT Master
VAV Master
Inhibit Heating Call from
No/Yes
this zone?
Active Heating Caller?
No/Yes
Inhibit Cooling Call from
No/Yes
this zone?
Active Cooling Caller?
No/Yes
Linkage RH Type
Avg/Max
Linkage IAQ Type
Avg/Max
Air Source Mode
Off
Warmup
Heat
Cool
Freecool
Pressure
Evac
Vent
Air Source Supply Air
°F
Temp
Air Source Static
in wc
Pressure
Air Source Outdoor Air
°F
Temp
Number of ProvidersIf
1 to 64
Master zone, set Number
of Providers to the total #
of controllers that will
report to the Master,
including the master
For a slave zone the # of
providers is 1
Air Source (RTU)
0 to 65,535
(Collector) Network #
Air Source Address Type MSTP or IP
MS/TP Address
0 to 137
RANGE
DEFAULT
1
0
0
Slave
No
No
Avg
Avg
1
0
MSTP
0
44