Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 51

With vav-rtu open controller
Table of Contents

Advertisement

Point Name
Supply Fan Relay State
Supply Fan Runtime
Supply Fan Runtime
Supply Fan Service Alarm Timer
Supply Fan Status
Supply Fan VFD
Switch Configuration
System Cooling Demand Level
System Heating Demand Level
System is shut down
System Mode
System OAT Master
System Outdoor Air Temperature
System Outdoor AQ
System Return Air Temperature
System Space AQ
System Space RH
System Space Temperature
Unocc Free Cool
Vent Dmpr Pos / DCV Min Pos
VFD Speed Test
ZS Sensor Configuration
APPENDIX D — BACNET POINTS LIST (CONT)
Table C — VAV-RTU Open Protocol Maps (cont)
Point
Access
R
R
hr
R
R/W
hr
R
R
%
R
R
no units
R
no units
R
R
1=Off
2=Fan Only
3=Economizer Cooling
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdow
9=Unocc Free Cooling
10=Fire Shutdown
11=IAQ Override
12=Pre-Occ Purge
13=IGC Override
R
°F
R/W
°F
R/W
ppm
R/W
°F
R/W
ppm
R/W
%rh
R/W
°F
R/W
R/W
%Open
R/W
%
R
Default
Units
Value
0
-999
-999
-999
-999
-999
-999
Inactive (0)
20
0
51
BACnet Point Name
sfan
BV:2001
sfan_rntm
AV:2014
sfan_rntm_alarm
BV:7010
sfan_service_hrs
AV:83005
sfan_status
BV:1003
vfd_output
AV:2027
di_cfg_alarm
BV:7025
cool_demand_level
AV:9006
heat_demand_level
AV:9036
shutdown_status
BV:2011
run_status
MSV:2002
mstr_oa_temp
AV:80001
system_oat
AV:1901
system_oaq
AV:1908
system_rat
AV:1920
system_iaq
AV:1903
system_rh
AV:1904
system_spt
AV:1902
ntfc_ena
BV:80001
econ_min
AV:9005
vfd_spd_test
AV:81002
zs_config_fail
BV:7055
BACnet
Object ID

Advertisement

Table of Contents
loading

This manual is also suitable for:

50lcb0748lcb2650lcb26