Access Level
Equipment Touch or
3 = ADMIN
System Touch Menu
2 = USER
1 = None
Property Pages>
3
Linkage (cont)
3
3
3
3
3
3
3
3
3
3
1 This input will only be shown if Input Configuration>Input 5, 8 or 9 Function is set to 3 = Fan Status
2 Displayed value that the VAV-RTU Open controller is controlling to
3 This input will only be shown if Input Configuration>Input 2 Function is set to 3 = Space RH Sensor and there is a valid Space Relative
Humidity value on J4 -2&3
4 This input will only be shown if Input Configuration>Input 2 Function is set to 2 = IAQ Sensor and there is a valid Indoor Air Quality CO
Sensor value on J4 -2&3
5 This input will only be shown if Input Configuration>Input 2 Function is set to 2 = OAQ Sensor, there is a valid Indoor Air Quality CO
Sensor value on J4 -2&3, and Service Configuration>DCV Control is set to Enable at one of the VAV Zone controllers which has Service
Configuration>Hardwired Sensor set to CO
6 Default to meet California Title 24 requirements is 45°F
7 Do Not Use
8 Input Switch Configuration must be set for each Input Function
9 This input will only be shown if Service Configuration>Heat Type is set to Electric. For gas units (Service Configuration> Heat Type set to
1 = Gas) (48 series units) this input is automatically set to 7 = IGC Override
10 This input will only be shown when a ZS sensor is connected to J13
11 This setpoint will only be shown if Service Configuration>SA Tempering is set to Enable
12 Compressor Stages default is Three Stages and cannot be changed
13 Economizer Exist default is Yes and cannot be changed
14 This configuration will only be shown if Input Configuration>Input 2 Function is set to 2 = IAQ Sensor
15 This configuration will only be shown if Input Configuration>Input 2 Function is set to 4 = OAQ Sensor
16 This input will only be shown if HPCO Shutdown is in alarm. This is the reset point for the alarm.
17 If using a Carrier Comfort Network
Instance can be 1, 2, 3, or 4, depending on the number of air sources used in the system.
APPENDIX A — USER INTERFACE MENUS (CONT)
Table A — User Interface Menus (cont)
POINT NAME
LINKAGE (cont)
Occupied Cooling
Setpoint
Occupied Heating
Setpoint
Unoccupied Cooling
Setpoint
Unoccupied Heating
Setpoint
Indoor Air CO
2
Space Relative Humidity xxx %
Linkage Optimal Start
The following information is sent back to the Zoning System Master Zone:
Air Source Mode
Air Source Supply Air
Temp
Air Source Static
Pressure
Air Source Outdoor Air
Temp
Sensor with a valid value on J4 - RH&Gnd
2
(CCN) and BACnet System (i.e., Carrier CCN Air Terminal to BACnet Air Source), the Application
®
RANGE
xxx °F
xxx °F
xxx °F
xxx °F
xxxx ppm
Inactive/Active
xxx °F
"wc
xxx °F
43
DEFAULT
Field Assistant Menu
Properties>
Control Program>
Linkage>
Airside Linkage (cont)
2
2