Access Level
Equipment Touch or
3 = ADMIN
System Touch Menu
2 = USER
1 = None
Property Pages>
Maintenance>
Unit (cont)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
APPENDIX A — USER INTERFACE MENUS (CONT)
Table A — User Interface Menus (cont)
POINT NAME
MAINTENANCE (UNIT) (cont)
RAT Source
Space Temp Source
Ctrl Temp Source
Occupancy Source
Effective Heat Setpoint
Effective Clg Setpoint
Relative Humidity Source 1 = N/A
IAQ Source
Outdoor Air Temperature
Source
OAQ Source
System Cooling Demand
Level
System Heating Demand
Level
System Status
Safety Chain Feedback
Fire Shutdown Status
Compressor Safety
Status
Calculated Min Econ Pos 0-100%
Calculated Min PE
Setpoint
Active Cooling Stages
RANGE
Sensor Failure
Local RAT
Net/Sys RAT
Locked Value
1 = N/A
2 = Local
3 = Network
4 = Linkage
5 = Locked Value
Sensor Failure
Space Temp
Return Air
Linkage Zone
Locked value
Override TLO
BACnet Schedule
BAS On / Off
Remote Occ Input
Linkage
°F
°F
2 = Local
3 = Network
4 = Linkage
5 = Locked Value
6 = Linkage & Local
7 = ZS Sensor
8 = Linkage & ZS Sensor
1 = N/A
2 = Local
3 = Network
4 = Linkage
5 = Locked Value
6 = Linkage & Local
7 = ZS Sensor
8 = Linkage & ZS Sensor
1 = N/A
2 = Local
3 = Network
4 = Linkage
5 = Locked Value
6 = Linkage & Local
7 = ZS Sensor
8 = Linkage & ZS Sensor
1 = N/A
2 = Local
3 = Network
4 = Linkage
5 = Locked Value
6 = Linkage & Local
7 = ZS Sensor
8 = Linkage & ZS Sensor
0 -3
0 - 3
1 = OA Econ unsuitable
2 = Free Cooling Avail
3 = Economizer Enabled
4 = Compressor Enabled
5 = Heating Enabled
6 = MA Low Limit Active
Off/Run Enabled
Run Enabled/Shutdown
Normal/Trouble
0-100%
0-2
40
DEFAULT
Field Assistant Menu
Properties>
Control Program>
Maintenance>
Unit (cont)