Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 49

With vav-rtu open controller
Table of Contents

Advertisement

Point Name
Factory Test Relay 3 Control
Factory Test Relay 4 Control
Factory Test Relay 5 Control
Factory Test Relay 6 Control
Factory Test Relay 7 Control
Factory Test Relay 8 Control
Fan Off Delay
Filter
Filter Runtime
Filter Service Alarm Timer
Filter Status
Fire / Smoke Shutdown
Fire Shutdown Status
Gas Valve
Heat 1 Runtime
Heat 1 Runtime
Heat 1 Service Alarm Timer
Heat 1Test
Heat 2 Runtime
Heat 2 Runtime
Heat 2 Service Alarm Timer
Heat 2Test
Heat Interlock Relay State
Heat Interlock Relay Test
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Heat Type
Heating Control Setpoint
Heating Lockout Temperature
HPCO Shutdown
Humidistat Input Status
IGC Override
Indoor Air Quality
Indoor Air Quality CO2 (ppm)
Indoor Air Quality Sensor
Input 2 Function
Input 3 Function
Input 3 Switch Configuration
Input 5 Function
Input 5 Switch Configuration
Input 8 Function
Input 8 Switch Configuration
Input 9 Function
Input 9 Switch Configuration
input_2
input_3
input_4
input_5
input_8
input_9
Local OAT Sensor
Low Fan Econ Min Pos
Max VFD Output
Maximum Heating SAT
Min VFD Output
Minimum Cooling SAT
Number Of Heat Stages
OAT sensor
Occ Relative Humidity Setpoint
Occupancy Contact
Occupancy Source
APPENDIX D — BACNET POINTS LIST (CONT)
Table C — VAV-RTU Open Protocol Maps (cont)
Point
Access
R/W
R/W
R/W
R/W
R/W
R/W
R/W
seconds
R
R
hr
R/W
hr
R
R
R
R
R
hr
R
R/W
hr
R/W
R
hr
R
R/W
hr
R/W
R
R/W
R
R
R/W
R
°F
R/W
°F
R
R
R
R
R
ppm
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
mA
R
R
R
R
R
R
R/W
%Open
R/W
%
R/W
°F
R/W
%
R/W
°F
R/W
R
°F
R/W
%rh
R
R
Default
Units
Value
Inactive (0)
Inactive (0)
Inactive (0)
Inactive (0)
Inactive (0)
Inactive (0)
90
600
0
Inactive (0)
0
Inactive (0)
Inactive (0)
Active (1)
65
1
1
1
2
1
2
1
1
1
33
100
120
25
45
2
60
49
BACnet Point Name
relay3_fac_test
BV:91003
relay4_fac_test
BV:91004
relay5_fac_test
BV:91005
relay6_fac_test
BV:91006
relay7_fac_test
BV:91007
relay8_fac_test
BV:91008
fan_delay_off
AV:9024
filter_alarm
BV:7017
filter_rntm
AV:2015
filter_service_hrs
AV:2019
filter_status
BV:1004
fire_alarm
BV:7007
firedown_status
BV:1005
igc_alarm
BV:7050
heat1_rntm
AV:2029
heat1_rntm_alarm
BV:7062
heat1_service_hrs
AV:83008
heat1_test
BV:81003
heat2_rntm
AV:2030
heat2_rntm_alarm
BV:7063
heat2_service_hrs
AV:83009
heat2_test
BV:81002
ht_interlock
BV:2012
hir_test
BV:81006
heat_1
BV:2003
heat_2
BV:2002
heat_type
BV:99002
htg_cntl_pt
AV:2034
oat_ht_lockout
AV:9003
sp_alarm
BV:7060
humstat_status
BV:1006
igcovr_status
BV:1022
iaq_alarm
BV:7005
iaq
AV:1009
iaq_sensor_fail
BV:7039
ai2_function
MSV:81002
di3_function
MSV:81003
di3_type
MSV:81013
di5_function
MSV:81005
di5_type
MSV:81015
di8_function
MSV:81008
di8_type
MSV:81018
di9_function
MSV:81009
di9_type
MSV:81019
ai_2
AI:1002
di_3
BI:1003
di_4
BI:1004
di_5
BI:1005
di_8
BI:1008
di_9
BI:1009
loc_oat_sensor_fail
BV:7003
econ_min_2
AV:9030
max_vfd_spd
AV:3026
sat_ht_max
AV:83004
min_vfd_spd
AV:3027
sat_cl_min
AV:83003
heat_stages
MSV:91004
ai_7
AI:1007
occ_dehum_stpt
AV:3011
occ_contact_status
BV:1007
occ_source
MSV:1002
BACnet
Object ID

Advertisement

Table of Contents
loading

This manual is also suitable for:

50lcb0748lcb2650lcb26

Table of Contents