APPENDIX A — USER INTERFACE MENUS (CONT)
Table A — User Interface Menus (cont)
POINT NAME
UNIT CONFIGURATION
Fan Mode
Power Fail Restart Delay 0-30 sec
Fan Off Delay
Occupied Heating
Supply Air Temp Reset
Reset Ratio
Reset Maximum Limit
SA Reset Humidity
Override
Humidity Override
Disable/Enable
Minimum Cooling SAT
6
Maximum Heating SAT
Vent Dmpr Pos / DCV
Min Pos
Low Fan Econ Min Pos
Economizer Purge Min
Pos
DCV Max Vent Damper
Pos
Static Pressure Reset
Enable
Maximum Damper
Position
Minimum Damper
Position
Maximum Reset
SP Reset Demand Level 1 = Not Active
Supply Fan Service
Alarm Timer
Comp 1 Service Alarm
Timer
Comp 2 Service Alarm
Timer
Filter Service Alarm
Timer
Heat 1 Service Alarm
Timer
Heat 2 Service Alarm
Timer
Cooling Lockout
Temperature
Economizer High OAT
Lockout Temp
Heating Lockout
Temperature
Unocc Free Cool
Min Setpoint Separation
RANGE
1 = Auto
Continuous
2 = Continuous
3 = Always On
5
5-120 sec
90
Disable/Enable
Disable
Disable/Enable
Disable
0-10
3
0 - 25°F
10
Disable/Enable
Disable
Disable
45 - 75°F
45
90 - 150°F
120
0-100% Open
20
0-100% Open
33
0-100% Open
40
0-75% Open
50
Disabled/Enabled
Enabled
0-100 % Open
80
0-100 % Open
50
0.00 to 2.00 "wc
0.25
Not Active
2 = Cool Dmd Lvl 1
3 = Cool Dmd Lvl 2
4 = Cool Dmd Lvl 3
0-9999 hr
600
0-9999 hr
0
0-9999 hr
0
0-9999 hr
600
0-9999 hr
0
0-9999 hr
0
-65 - 80°F
45
55 - 80°F
75
35 - 150°F
65
Disable/Enable
Disable
2-10Δ°F
36
DEFAULT
Field Assistant Menu
Properties> Control
Program>
Configuration>Unit
Configuration