Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 6

With vav-rtu open controller
Table of Contents

Advertisement

POINT NAME
Return Air Temperature
Space Temperature
Supply Air Temperature
Outdoor Air Temperature
Static Pressure Sensor
Safety Chain Feedback
Compressor Safety Status
(1)
Fire Shutdown Status
Enthalpy Status
Zone Temperature
Indoor Air CO
2
Outdoor Air CO
2
Space Relative Humidity
Supply Fan Status
(2)
Filter Status
(2)
IGC Override
(2)
Economizer Output
Supply Fan VFD
Supply Fan Relay State
Cool Stage 1 Relay State
Cool Stage 2 Relay State
Cool Stage 3 Relay State
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Power Exhaust Relay State
Heat Interlock Relay State
(1) Safety Chain Feedback: 24Vac required at this terminal to provide "Run Enable" status. See Input/Output section for additional instructions.
(2) These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Sec-
tion for wiring and setup instructions.
(3) Parallel pins J5 - 1 = J2 - 6, J5 - 3 = J1 - 10, J5 - 5 = J1 - 2 are used for field installation.
(4) Refer to the input configuration and accessory sections for more detail.
Table 1 — VAV-RTU Open Inputs and Outputs
BACnet OBJECT NAME
DEDICATED INPUTS
ra_temp
n/a
sa_temp
oa_temp
static_press
safety_status
comp_status
firedown_status
enthalpy_status
n/a
CONFIGURABLE INPUTS
iaq
oaq
space_rh
sfan_status
filter_status
igcovr_status
econ_output
vfd_output
sfan
BO Relay (24VAC, 1A)
comp_1
BO Relay (24VAC, 1A)
comp_2
BO Relay (24VAC, 1A)
comp_3
BO Relay (24VAC, 1A)
heat_1
BO Relay (24VAC, 1A)
heat_2
BO Relay (24VAC, 1A)
pexh
BO Relay (24VAC, 1A)
ht- interlock
BO Relay (24VAC, 1A)
CONNECTION PIN
TYPE OF I/O
AI (10K Thermistor)
AI (10K Thermistor)
AI (10K Thermistor)
AI (10K Thermistor)
AI (4- 20 mA)
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
n/a
(4)
AI (4- 20 mA)
AI (4-20 mA)
AI (4- 20 mA)
BI (24 VAC)
J5-1 and 2 or J5-3 and 4,
BI (24 VAC)
J5-5 and 6 or J5-7 and 8
BI (24 VAC)
OUTPUTS
AO (4-20mA)
AO (2- 10Vdc)
J11-2 and 3 (N.O.)
6
CHANNEL DESIGNATION
NUMBER(S)
J20- 3 and 4
Analog Input 11
J20-1 and 2
Analog Input 10
J2- 1 and 2
Analog Input 6
J2- 3 and 4
Analog Input 7
J4- 4 and 5
Analog Input 1
J1- 9
Binary Input 4
J1- 2
Binary Input 3
J1- 10
Binary Input 5
J2- 6 and 7
Binary Input 8
J13- 1- 4
J4-2 and 3
Analog Input 2
Binary Input 3, 5, 8, or 9,
except where intrinsic input
Binary Input 3, 5, 8, or 9,
except where intrinsic input
(3)
Binary Input 9. Mandatory
input on gas heat units.
J2- 4 and 5
Analog Output 1
J22- 1 and 2
Analog Output 2
J1- 4
Binary Output 1 (G)
J1- 8
Binary Output 5 (Y1)
J1- 7
Binary Output 4 (Y2)
J11- 5 and 6
Binary Output 7 (Y3)
J1- 6
Binary Output 3 (W1)
J1- 5
Binary Output 2 (W2)
Binary Output 8 (PE)
J11- 7 and 8
Binary Output 6 (HIR)
Rnet
is used
is used