Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 59

With vav-rtu open controller
Table of Contents

Advertisement

POINT NAME
Occ High CO
Alarm Limit
2
Compressor Stages
9
Economizer Exists
10
VFD Input
Max VFD Output
Min VFD Output
Heat Type
Number of Heat Stages
SA Tempering
Continuous Occupied Exhaust
DCV Control
Indoor CO
Sensor Value @ Min mA
2
Indoor CO
Sensor Value @ Max mA
2
Outdoor CO
Sensor Value @ Min mA
2
Outdoor CO
Sensor Value @ Max mA
2
Static Pressure Sensor Value @ Min mA
Static Pressure Sensor Value @ Max
mA
System Space RH
System Space AQ
System Cool Demand Level
System Heat Demand Level
System Outdoor Air Temperature
System Outdoor AQ
System Fire / Smoke
Network Heat Interlock
Service Test Mode
Service Test
Fan Test
Compressor 1 Test
Compressor 2 Test
Heat 1 Test
Heat 2 Test
Heat Interlock Relay Test
Power Exhaust Test
Economizer Test
VFD Speed Test
Linkage Collector
13
Airside Linkage Status
Occupancy Status
Space Temperature
Occupied Cooling Setpoint
Occupied Heating Setpoint
Unoccupied Cooling Setpoint
Unoccupied Heating Setpoint
Indoor Air CO
2
Space Relative Humidity
Linkage Optimal Start
Air Source Mode
Air Source Supply Air Temp
Air Source Static Pressure
Air Source Outdoor Air Temp
RANGE
IAQ / VENTILATION ALARM
0-9999 ppm
SERVICE CONFIGURATION
N/A
N/A
0-10Vdc/2-10Vdc
15-100%
15-100%
0 = Electric (50 series units)
1 = Gas (48 series units)
1 = 1 stage (All 50LC*B07-09 units,
50LC*B12-14 lo heat)
2 = 2 stages (All 48LC*B07-26 units,
50LC*B12 hi heat, 50LC*B14
med/hi heat, All 50LC*B17-26 units)
Disabled/Enabled
No/Yes
Disable/Enable
0-9999ppm
11
0-9999ppm
11
0-9999ppm
12
0-9999ppm
12
N/A
N/A
0-3
0-3
N/A
N/A
Off/On
Off/On
SERVICE TEST
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
0-100 %Open
0-100%
Active/Not Active
Unoccupied/Occupied
xxx °F
xxx °F
xxx °F
xxx °F
xxx °F
xxxx ppm
xxx %
Inactive/Active
xxx °F
"wc
xxx °F
DEFAULT
1200
Three Stages
Yes (FIOP)
2-10Vdc
100
25
Gas
2
Disable
No
Disable
0
2000
0
2000
0
2.5
-999.0
-999.0
0
0
-999.0
-999.0
Off
Off
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
0
0
LINKAGE
CL-3
ENTRY