Carrier 48LCB07 Controls, Start-Up, Operation And Troubleshooting page 57

With vav-rtu open controller
Table of Contents

Advertisement

RTU Model Number:
RTU Serial Number:
RTU Open Software Version:
Protocol and Baud Rate:
POINT NAME
Fan Mode
Power Fail Restart Delay
Fan Off Delay
Occupied Heating
Supply Air Temp Reset
Reset Ratio
Reset Maximum Limit
SA Reset Humidity Override
Humidity Override Disable/Enable
Minimum Cooling SAT
1
Maximum Heating SAT
Vent Dmpr Pos / DCV Min Pos
Low Fan Econ Min Pos
Economizer Purge Min Pos
DCV Max Vent Damper Pos
Static Pressure Reset Enable
Maximum Damper Position
Minimum Damper Position
Maximum Reset
SP Reset Demand Level
Supply Fan Service Alarm Timer
Comp 1 Service Alarm Timer
Comp 2 Service Alarm Timer
Filter Service Alarm Timer
Heat 1 Service Alarm Timer
Heat 2 Service Alarm Timer
Cooling Lockout Temperature
Economizer High OAT Lockout Temp
Heating Lockout Temperature
Unocc Free Cool
Min Setpoint Separation
Input 2 Function
Input 3 Function
Input 3 Switch Configuration
8
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480277-01
RTU OPEN CONTROLLER START-UP SHEET
RANGE
UNIT CONFIGURATION
1 = Auto
2 = Continuous
3 = Always On
0-30 sec
5-120 sec
Disable/Enable
Disable/Enable
0-10
0 - 25°F
Disable/Enable
Disable
45 - 75°F
90 - 150°F
0-100% Open
0-100% Open
0-100% Open
0-75% Open
Disabled/Enabled
0-100 % Open
0-100 % Open
0.00 to 2.00 "wc
1 = Not Active
2 = Cool Dmd Lvl 1
3 = Cool Dmd Lvl 2
4 = Cool Dmd Lvl 3
0-9999 hr
0-9999 hr
0-9999 hr
0-9999 hr
0-9999 hr
0-9999 hr
-65 - 80°F
55 - 80°F
35 - 150°F
Disable/Enable
2-10Δ°F
INPUT CONFIGURATION
1 = No Sensor
2 = IAQ Sensor
3 = Space RH Sensor
4 = OAQ Sensor
1 = No Function
2 = Compressor Safety
3 = Fan Status
4 = Filter Status
5 = Remote Occupancy
2
6 = Door Contact
7
1 = NO (Normally Open)
2 = NC (Normally Closed)
Printed in U.S.A.
Form 48-50LCB-7-26-02T Rev. A
Date:
Performed by:
Company:
Network Address:
DEFAULT
Continuous
5
90
Disable
Disable
3
10
Disable
45
120
20
33
40
50
Enabled
80
50
0.25
Not Active
600
0
0
600
0
0
45
75
65
Disable
No Sensor
No Function
NO
Pg CL-1
ENTRY
3-2020 Replaces: 48-50LCB-7-26-01T