iBoot-30A
Command Line Interface
The iB-30 Command Line Interface (CLI) provides a text based method for communicating with the
iBoot. The syntax of the CLI uses a basic Set (change a variable) and Get (retrieve a variable). The
CLI is accessed through the Telnet protocol and requires a Telnet client program.
To access the CLI
Open the Telnet client and connect to the IP address set for the iBoot.
Once the conection is made the User: login prompt is presented.
Enter user or admin and press Enter. The prompt will change to Password:.
Enter the admin or user password and press Enter. The prompt will change to iBoot>. This indicates
successful login. Enter commands as needed. When done, enter the logout command.
Command
CONTROL COMMANDS
set outlet <on | off | cycle>
get outlet
DEVICE COMMANDS
get location
set location <20 char. max>
set upgrade enable <yes | no>
get upgrade enable
logout
reboot
NETWORK COMMANDS
get network
iBoot-30a_v101118e
iB-30 CLI Syntax
Description
These commands are used to monitor and control the outlet.
This command controls the outlet.
This command returns the current status of the outlet.
These commands are available to the administrator only
This command returns the iB-30's location ID.
This command is used to set the iB-30's location ID.
Enables or disables the ability to upload new firmware to
the iB-30.
This command displays the upload enable status.
Terminates the session
This command reboots the iB-30.
All set commands require a reboot before they take effect.
These commands are only available to the administrator.
This command will return all the network settings as
shown below:
Mode: static
IP Address: 192.168.1.254
Subnet Mask: 255.255.255.0
Gateway: 192.168.1.1
HTTP Port: 80
Telnet Port: 23