Symptom
Igniter lights but heater does
not fire

11.2 Service Diagnostic Messages

The controller monitors several functions of the heater. In the event of a malfunction, the controller will display a
FAULT message. The following table lists the Heater Service Messages along with potential causes and remedies.
Fault Message
CHECK FLOW
FAULT-
HIGH LIMIT
FAULT - HIGH FLUE
TEMPERATURE
FAULT-
CHECK IGN CONTROL
FAULT-
SHORTED H2O SENSOR
or
FAULT-
OPEN WATER SENSOR
FAULT-
PUMP
AUX Monitor
|
Installation & Operation Manual
Possible Cause
Gas valve is not ON.
Air in gas line.
No power to gas valve.
Low gas pressure/volume.
High burner throat pressure.
Gas valve failed.
Possible Cause
Pump is not running.
Low pump pressure.
Pressure switch fault.
Variable speed pump set too low.
Water temperature in heater exceeds
the internal limit.
Limit switch fault.
Flue temp limit fault
Broken, split, pinched or disconnected
air pressure switch tubing.
Fan not operating.
Fan running slow
Premature fan failure.
Air flow restricted at intake or discharge.
Broken igniter.
Low gas supply pressure/volume.
No flame at burner.
Faulty wiring or connection.
Failed water temperature sensor.
Status message indicating the filter
pump is currently turned OFF when the
heater system programmed in Maintain
Temp mode.
ENGLISH
Remedy
Flip the switch to "on" position.
Cycle ignition sequence until air is out of the gas line.
Check controls for proper operation.
Check supply pressure/volume and verify proper gas
supply pipe size.
Replace gas valve.
NOTE: Gas valve failures are extremely rare. Please
confirm this as the root problem before replacing.
Remedy
Check breakers and power source, recheck wiring, set
time clock and current time.
Clean filter or clear blockage, check position of valve in
plumbing system.
Make sure return eyeball fittings are installed on the
wall of the pool.
Adjust or replace pressure switch.
Adjust variable speed pump.
Refer to qualified service personnel.
Inspect vent for obstructions or blockages.
Indoor installations, check vent pipe for bird, insect or
rodent activity that could cause a blockage.
Replace switches.
Refer to qualified service personnel.
Identify and correct loose connections.
Replace flue sensor.
Refer to qualified service personnel.
Check tubing and replace if necessary.
Correct fault or replace fan.
Replace igniter.
Verify proper wiring for 120 VAC or 240 VAC.
Check for proper clearances around heater and for
adequate room ventilation if enclosed. Inspect for
blockage or restriction at discharge of flue.
Check ignition control LED codes (see Section 10.3,
Ignition Control LED Service Codes).
Verify that the size, length and number of elbows on the
gas supply line meet national codes.
Identify and correct loose wiring connections, or
problems with igniter, gas valve, or ignition control.
Refer to qualified service personnel.
Inspect water temperature sensor wiring.
Ensure sensor is connected correctly into the power
interface board (PIB).
Replace water temperature sensor.
Refer to qualified service personnel.
No Service Required. This is normal when the control
is in a Maintain Temp mode.
Check VersaFlo