Fault Indicator (Yellow) Lights Up Or Blinks - Panasonic SF4С Series Instruction Manual

Safety light curtain
Hide thumbs Also See for SF4С Series:
Table of Contents

Advertisement

Troubleshooting

6.2.4 Fault Indicator (Yellow) Lights up or Blinks

Error
[Digital error indicator:
Error in the setting data of SF4C
[Digital error indicator:
System error between emitter
and receiver
[Digital error indicator:
Extraneous light error
[Digital error indicator:
Control output (OSSD1/2) data
error
[Digital error indicator:
Wiring error of the output polarity
setting wire (shield)
[Digital error indicator:
External device error
108
SEN TRONIC
AG
Produkte, Support und Service
Cause
]
Noise is outside the specified range.
Internal error
]
Different types of emitter and receiver
have been connected
]
Extraneous light is entering or light from
other model is entering.
Control output 1 (OSSD 1) wire (black)
or control output 2 (OSSD 2) wire
(white) is short-circuited.
Control output 1 (OSSD 1) wire (black)
or control output 2 (OSSD 2) wire
(white) is not correctly wired or is wired
with other I/O wires.
Excessive incoming current flows in
]
control output 1 (OSSD 1) wire (black)
or control output 2 (OSSD 2) wire
(white).
The output polarity setting wire (shield),
the control output 2 (OSSD 2) wire
(white) is not correctly wired.
Output circuit error.
]
• The output polarity setting wire
(shield) comes down or
short-circuits with other I/O wires.
The output polarity setting wire
(shield) connection of the
emitter/receiver is incorrect.
]
When using the
safety relay
Rugghölzli 2
CH - 5453 Busslingen
Remedy
Check the noise status around this
device.
Replace this device.
Only pair up emitters and
receivers of the same type, i.e.
with the same number of beam
channels.
When the power is on, prevent any
extraneous light from entering the
receiver, if the extraneous light is
coming from other models see
"Device Placement" on page 22.
Wire the control output 1 (OSSD 1)
wire (black) and the control output
2 (OSSD 2) (white) correctly.
The current value for the control
outputs should be within the
specified range "Wiring" on page
34.
Wire the output polarity setting
wire (shield) correctly.
(0V: PNP, +V: NPN output)
Wire the output polarity setting
wire (shield) of the receiver
correctly "Wiring" on page 34.
The output circuit is damaged.
Replace this device.
Wire the wire output polarity
setting (shield) correctly.
(0V: PNP output, +V: NPN output)
Relay contact is
Replace the relay.
welded.
Response time of
Replace the relay with a proper
the relay is slow.
response time (see page 73).
Contact point "b"
Wire the contact point correctly.
of the relay is not
wired.