SF4C Safety light curtain

3.7 External Device Monitor Function

This is the function for checking whether the external safety relay connected to the control
output (OSSD 1, OSSD 2) performs normally in accordance with the control output (OSSD 1,
OSSD 2) or not. If any abnormality such as a deposit on the contacting point, etc. is detected,
the status of the sensor changes to lockout and the control output (OSSD 1, OSSD 2) is turned
to OFF.
When the external device monitor function is activated:
Connect the external device monitor input to the external safety relay of the control
output (OSSD 1, OSSD 2).
When the external device monitor function is deactivated:
Connect the external device monitor input to the auxiliary output. By default, the
auxiliary output is set to negative logic of the control output (OSSD 1, OSSD 2). The
setting can be changed with the handy controller. In this case, the auxiliary output
cannot be connected to external devices.
NOTE
You can deactivate the external device monitor function or change the time
range with the handy controller.
Beam
Reception status
received
Beam
blocked
ON
Control output
(OSSD 1, OSSD 2)
OFF
ON
External device
monitor input
OFF
Time diagram - normal operation
The setting time of the device monitor is 300ms or less. Exceeding 300ms turns the device into
the lockout status.
Beam
Reception status
received
Beam
blocked
ON
Control output
(OSSD 1, OSSD 2)
OFF
ON
External device
monitor input
OFF
SEN TRONIC
AG
Produkte, Support und Service
7ms or less
90ms or less
300ms or less
7ms or less
300ms
Rugghölzli 2
Tel. +41 (0)56 222 38 18
CH - 5453 Busslingen
Fax +41 (0)56 222 10 12
3.7 External Device Monitor Function
300ms or less
Lockout status
mailbox@sentronic.com
73
www.sentronic.com