3�3�1�1�- Scale selection
The FLEX Wibeee 25 current sensors indicate the selected scale through the blue LED on
their head.
During the first 20 seconds after being switched on, the Wibeee Max is in the scale selection
period. The blue LED flashes quickly and indicates the selected scale.
Press the RESET key during this period to select the desired scale:
One blink indicates that the 350 A scale has been selected.
Two blinks indicate that the 700 A scale has been selected.
When the scale selection period has ended, the quick blinking light is deactivated and the blue
LED indicates the selected scale at regular intervals.
3�3�2�- Wibeee Max Plus
In the Wibeee Max Plus model, current measurement is performed using the FLEX Wibeee
54 flexible sensors.
Measurement scales
Nominal range
Output / input ratio
Range of use
Specified measurement range
Typical phase difference
The measurement uncertainty is for the sensor in its optimal position, with no external electric
or magnetic fields and within the working temperature range,
Instruction Manual
Table 6:Metrological characteristics�
FLEX Wibeee 54
100
100 A
10.0 mV/A
1 ... 100 A
10 ... 100
1st
Table 7:Position error
Position
A
B
A
B
1 k
1000 A
5000 A
1.0 mV/A
0.2 mV/A
10 ... 1000 A
50 ... 5000 A
100 ... 1000
500 ... 5000
1st
Table 7�
Error
± 1%
A ± 3%
5 k
1st
11