FLOOR-STANDING MFZ-KA
C.2.12 CAPACITY CORRECTION RATIO CURVE PIPING LENGTH
Correction ratio of capacity according to the length of piping (cooling)
100%
99%
98%
97%
96%
95%
94%
93%
92%
91%
90%
89%
88%
87%
86%
85%
0
5
Actual length of refrigerant piping (m)
Correction ratio of capacity according to the length of piping (heating)
100%
99%
98%
97%
96%
95%
0
5
Actual length of refrigerant piping (m)
The length intended for the capacity calculation, which counts the length of refrigerant piping and
the number of bends, is called actual length.
Length of refrigerant piping (m) + ( Number of bends × 0.3 m ) = Actual length of refrigerant piping (m)
C-274
VA Series
•
Indoor unit
25 class
Indoor unit
35 class
10
15
20
25
All capacity class
10
15
20
25
Indoor unit
50 class
30
35
30
35
M series