M series
MOUNTING ARRANGEMENT OF DRAIN SOCKET
Please perform the drain piping work only when draining from one place.
1) Choose one hole to discharge drain and install the drain socket to the hole.
2) Close the rest of the holes with the drain caps.
3) Connect a vinyl hose of 15 mm in the inside diameter on the market with the drain socket and lead drain.
Note:
Install the unit horizontally.
Do not use the drain socket in the cold regions. Drain may freeze and it makes the fan stop.
The outdoor unit produces condensate during the heating operation. Select the installation place to ensure to prevent the outdoor unit and/or the grounds
from being wet by drain water or damaged by frozen drain water.
CONNECTING WIRES FOR OUTDOOR UNIT
1) Remove the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting
wire (B) from the indoor unit correctly on the terminal block. Be careful
not to make mis-wiring. Fix the wire to the terminal block securely so
that no part of its core is appeared, and no external force is conveyed
to the connecting section of the terminal block.
3) Firmly tighten the terminal screws to prevent them from loosening. Af-
ter tightening, pull the wires lightly to confirm that they do not move.
4) Perform 2) and 3) for each indoor unit.
5) Connect power supply cord (A).
6) Fix indoor/outdoor unit connecting wire (B) and power supply cord (A)
with the cable clamps.
7) Close the service panel securely. Make sure that 3-2. PIPE CONNEC-
TION is completed.
• After making connections between both power supply cord (A) and
indoor/outdoor unit connecting wire (B), be sure to fix both cable and
wire with cable clamps.
Indoor/outdoor unit connecting wire
Terminal
block
UNIT
*D unit is for 4B71VA only
• Be sure to attach each screw to its correspondent terminal when securing the cord and/or the wire to the terminal block.
• Make earth wire a little longer than others. (More than 35 mm)
• For future servicing, give extra length to the connecting wires.
Terminal
Terminal
block
block
*
UNIT
UNIT
<INDOOR UNIT>
MULTI SYSTEM Inverter Heat Pump
Service panel
<OUTDOOR UNIT>
Terminal
Terminal block for
block
power supply
POWER SUPPLY
~/N 230 V 50 Hz
UNIT
Terminal block
for power supply
4B71VA
D unit is for 4B71VA only
15 mm
35 mm
Lead wire
C-555