M series
MSZ-FD50VA MSZ-FD50VAS
MUZ-FD50VA MUZ-FD50VABH
SPECIFICATIONS
Model
Indoor unit
Outdoor unit
MSZ-FD50VA(S)
MUZ-FD50VA(BH)
*1 Connect to the power switch which has a gap of 3 mm or
more when open to interrupt the source power phase. (When
the power switch is shut off, it must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57. The unit
shall be installed in accordance with national wiring regulations.
*3 Never use pipes with thickness less than specified. The
pressure resistance will be insufficient.
INSTALLATION DIAGRAM
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate
Installation plate fixing screw
(2)
4 × 25 mm
(3) Remote controller holder
Fixing screw for (3) 3.5 × 16 mm
(4)
(Black)
(5) Battery (AAA) for (6)
(6) Wireless remote controller
Felt tape
(7)
(For left or left-rear piping)
(8) Plasma anti-allergy enzyme filter
(9) Plasma deodorizing filter
<Outdoor unit>
(10) Drain socket (VA type only)
(11) Drain cap ø 33 (VA type only)
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*
(B) Extension pipe
(C) Wall hole sleeve
(D) Wall hole cover
(E) Pipe fixing band
(F) Fixing screw for (E) 4 × 20 mm
(G) Piping tape
(H) Putty
Drain hose
(I)
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
(J) Refrigeration oil
(K) Power supply cord*
* Note:
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away
from the TV antenna wire.
Units should be installed by licensed contractor
according to local code requirements.
Power supply *1
Rated
Breaker
Frequency
Voltage
capacity
230 V
50 Hz
16 A
*4 Use a copper pipe or a copper-alloy seamless pipe.
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
*7 If pipe length exceeds 7 m, additional refrigerant (R410A)
charge is required. (No additional charge is required for
pipe length less than 7 m.)
1
5
1
2
2
1
1
1
1
1
2
1
1
1
1
2 to 5
2 to 5
1
1
1 or 2
1
1
Appearance of the outdoor unit may differ from some
models.
WALL-MOUNTED Inverter Heat Pump
Pipe size
Wire specifications *2
(thickness *3, *4)
Indoor/outdoor
Power supply
Gas / Liquid
connecting wire
3-core
4-core
ø12.7 / 6.35 mm
2.0 mm
2
1.0 mm
2
(0.8 mm)
*8 Insulation material : Heat resisting foam plastic 0.045
*9 Be sure to use the insulation of specified thickness. Exces-
Be sure to use wall hole
sleeve (C) to prevent
indoor/outdoor connecting
wire (A) from contacting
metal parts in the wall and
to prevent damage by
rodents in case the wall is
hollow.
After the leak test, apply
insulating material tightly
so that there is no gap.
When the piping is to be at-
tached to a wall containing
metals (tin plated) or metal
netting, use a chemically
treated wooden piece 20
mm or thicker between the
wall and the piping or wrap
7 to 8 turns of insulation vi-
nyl tape around the piping.
To use existing piping, per-
form COOL operation for
30 minutes and pump down
before removing the old air
500 mm
conditioner. Remake flare
or more
according to the dimension
for new refrigerant.
(10)
(11)
Note:
Install the unit horizontally.
Do not use drain socket (10) in cold regions. Drain may freeze and
make the fan stop.
The outdoor unit produces condensate during the heating operation.
Select the installation place to ensure to prevent the outdoor unit and/
or the grounds from being wet by drain water or damaged by frozen
drain water.
Pipe length and height difference
Max. pipe length
Max. height difference
Max. number of bends *5, *6
Refrigerant adjustment A *7
Insulation thickness *8, *9
Additional refrigerant = A × (pipe length (m) - 7)
specific gravity
sive thickness may cause incorrect installation of the indoor
unit and insufficient thickness may cause dew drippage.
Wall hole cover (D)
Indoor unit
Seal the wall hole
gap with putty (H).
Wall hole
sleeve (C)
Fix the pipe to wall
with pipe fixing
band (E).
Cut off the
Pipe fixing band
extra length.
(E)
Outdoor unit installation
840 mm
169
500 mm
mm
Air inlet
Air outlet
4-10 mm × 21 mm slot
Drain piping for outdoor unit
<VA type only>
• Provide drain piping before indoor and
outdoor piping connection.
• Connect drain hose (I) I.D.15 mm as
shown in the illustration.
(I)
• Choose one hole for draining, and install
drain socket (10). Close the remaining
two holes with drain cap (11).
• Make sure to provide drain piping with a
downhill grade for easy drain flow.
30 m
15 m
10
30 g/m
8 mm
Fixing screw
(F)
40 mm
C-183