WALL-MOUNTED Cooling Only/Fixed Speed Heat Pump
MS-GE50VB
MSH-GE50VB
MU-GE50VB
MUH-GE50VB
SPECIFICATIONS
Model
Rated
Indoor unit
Outdoor unit
Voltage
MS(H)-GE50VB MU(H)-GE50VB 230 V
*1 Connect to the power switch which has a gap of 3 mm or
more when open to interrupt the source power phase. (When
the power switch is shut off, it must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57.
*3 Never use pipes with thickness less than specified. The
pressure resistance will be insufficient.
INSTALLATION DIAGRAM
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate
Installation plate fixing screw
(2)
4 × 25 mm
(3) Remote controller holder
Fixing screw for (3)
(4)
3.5 × 16 mm (Black)
(5) Battery (AAA) for (6)
(6) Wireless remote controller
Felt tape
(7)
(For left or left-rear piping)
<Outdoor unit>
(8) Drain socket <MSH type only>
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*
(B) Extension pipe
(C) Wall hole sleeve
(D) Wall hole cover
(E) Pipe fixing band
(F) Fixing screw for (E) 4 x 20 mm
(G) Piping tape
(H) Putty
Drain hose
(I)
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
(J) Refrigeration oil
(K) Power supply cord*
* Note:
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away
from the TV antenna wire.
Units should be installed by licensed contractor
according to local code requirements.
C-170
Power supply *1
Breaker capacity
Indoor Power
Frequency
(Indoor/outdoor)
supply cord
3-core
50 Hz
10 / 15 A
1.0 mm
*4 Use a copper pipe or a copper-alloy seamless pipe.
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
*7 If pipe length exceeds 7 m, additional refrigerant (R410A)
charge is required. (No additional charge is required for
pipe length less than 7 m.)
1
7
1
2
2
1
1
1
1
1
1
1
2 to 5
2 to 5
100 mm
1
or more
1
1 or 2
1
1
200 mm or more
Appearance of the outdoor unit may differ from some models.
Pipe size
Wire specifications *2
(thickness *3, *4)
Outdoor Power
Indoor/outdoor
Gas / Liquid
supply
connecting wire
3-core
2
1.5 mm
2-core
ø12.7 / 6.35 mm
(10 m or less)
2
2
1.0 mm
(0.8 mm)
2.5 mm
2
(15 m or less)
Additional refrigerant = A × (pipe length (m) - 7)
*8 Insulation material : Heat resisting foam plastic 0.045 spe-
cific gravity
*9 Be sure to use the insulation of specified thickness. Exces-
sive thickness may cause incorrect installation of the indoor
unit and insufficient thickness may cause dew drippage.
Cut off
the extra
length.
After the leak test, apply
insulating material tightly
so that there is no gap.
When the piping is to be
attached to a wall contain-
ing metals (tin plated) or
metal netting, use a chemi-
cally treated wooden piece
20 mm or thicker between
the wall and the piping or
wrap 7 to 8 turns of insula-
tion vinyl tape around the
piping.
To use existing piping, per-
form COOL operation for
30 minutes and pump down
before removing the old air
conditioner. Remake flare
according to the dimension
for new refrigerant.
(8)
Space for indoor unit working
Please leave the space as shown in the
picture for maintenance usage.
M series
Pipe length and height difference
Max. pipe length
Max. height difference
Max. number of bends *5, *6
Refrigerant adjustment A *7
Insulation thickness *8, *9
Wall hole cover (D)
Indoor
Pipe fixing
Seal the wall hole
unit
band (E)
gap with putty (H).
Wall hole
Fixing
Fix the pipe to
sleeve (C)
screw (F)
wall with pipe
fixing band (E).
Be sure to use wall hole sleeve (C) to
prevent indoor/outdoor connecting wire
(A) from contacting metal parts in the
wall and to prevent damage by rodents
in case the wall is hollow.
Outdoor unit installation
800 mm
150
500 mm
mm
Air inlet
Air outlet
2/4-10 mm × 21mm slot
40 mm
Drain piping for outdoor unit
<MSH type only>
• Provide drain piping before indoor and
outdoor piping connection.
• Connect drain hose (I) I.D.15 mm as
shown in the illustration.
• Make sure to provide drain piping with
a downhill grade for easy drain flow.
(I)
Note:
Install the unit horizontally.
Do not use drain socket (8) in cold regions.
Drain may freeze and make the fan stop.
The outdoor unit produces condensate
during the heating operation. Select the in-
stallation place to ensure to prevent the
outdoor unit and/or the grounds from being
wet by drain water or damaged by frozen
drain water.
100 mm or more
Installation
Indoor unit
plate
25 m
10 m
10
20 g/m
8 mm
Space

Hide quick links: